Drinking water in Husum, Schwesing, Simonsberg, Südermarsch und Spaltenhof
One supply zone, water supplier: Stadtwerke Husum Netz GmbH.
How to read the share of the parametric value
Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.
Wasserwerk Mildstedt, Pumpenhaus Werkausgang (Reinwasser, Husum 2)
Stadtwerke Husum Netz GmbHAssigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Nitrate | 0,827 mg/l | 50 mg/l | 2 % | Single value |
| Escherichia coli (E. coli) | 0 KBE/100ml | 0/100 ml | — | Single value |
| Sulphate | 42 mg/l | 250 mg/l | 17 % | Single value |
| Sodium | 25,9 mg/l | 200 mg/l | 13 % | Single value |
Show all recorded parameters (31 — most recent value per parameter)
Microbiology (1)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Escherichia coli (E. coli) | 0 KBE/100ml | 0/100 ml | — | Single value |
Chemical parameters (2)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Nitrate | 0,827 mg/l | 50 mg/l | 2 % | Single value |
| Nitrite | <0,005 (+) mg/l below limit of quantification | 0.5 mg/l | < 1 % * | Single value |
* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.
Indicator parameters (18)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Aluminium | <0,01 mg/l below limit of quantification | 0.2 mg/l | < 5 % * | Single value |
| Ammonium | <0,005 (NWG) mg/l not detectable | 0.5 mg/l | — | Single value |
| Calcite dissolution capacity | -1 mg/l | 5 mg/l CaCO3 | — | Single value |
| Chloride | 60 mg/l | 250 mg/l | 24 % | Single value |
| Coliform bacteria | 0 KBE/100ml | 0/100 ml | — | Single value |
| Colony count 22 °C | 0 KBE/ml | ohne anormale Veränderung | — | Single value |
| Colony count 36 °C | 0 KBE/ml | ohne anormale Veränderung | — | Single value |
| Colour | farblos Unit not stated in the document | 0.5 m⁻¹ | — | Single value |
| Conductivity (25 °C) | 577 µS/cm | 2,790 µS/cm | — | Single value |
| Iron | <0,003 (NWG) mg/l not detectable | 0.2 mg/l | — | Single value |
| Manganese | <0,002 (NWG) mg/l not detectable | 50 µg/l | — | Single value |
| Odour | ohne | für den Verbraucher annehmbar | — | Single value |
| pH | 7,86 | 6,5–9,5 | — | Single value |
| Sodium | 25,9 mg/l | 200 mg/l | 13 % | Single value |
| Sulphate | 42 mg/l | 250 mg/l | 17 % | Single value |
| Temperature | 19,2 °C | — | — | Single value |
| Total organic carbon (TOC) | 1,2 mg/l | ohne anormale Veränderung | — | Single value |
| Turbidity | keine Unit not stated in the document | 1 NTU | — | Single value |
* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.
Further parameters (10)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Acid capacity to pH 4.3 | 3,29 mmol/l | — | — | Single value |
| Base capacity to pH 8.2 | 0,21 mmol/l | — | — | Single value |
| Calcium | 83,1 mg/l | — | — | Single value |
| Carbonate hardness | 9,1 °dH | — | — | Single value |
| Free carbon dioxide | 10 mg/l | — | — | Single value |
| Hardness range (WRMG) | mittel | — | — | Single value |
| Hydrogen carbonate | 197,7 mg/l | — | — | Single value |
| Magnesium | 4,16 mg/l | — | — | Single value |
| Potassium | 1,36 mg/l | — | — | Single value |
| Total hardness | 2,24 mmol/l | — | — | Single value |
Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.
Postcodes in this zone: 25813
Frequently asked questions about drinking water in Husum, Schwesing, Simonsberg, Südermarsch und Spaltenhof
- How hard is the water in Husum, Schwesing, Simonsberg, Südermarsch und Spaltenhof?
- Stadtwerke Husum Netz GmbH publishes a total hardness of 2,24 mmol/l for the supply zone Wasserwerk Mildstedt, Pumpenhaus Werkausgang (Reinwasser, Husum 2) — that corresponds to 12.6 °dH. The hardness range is a classification under the German Detergents and Cleaning Products Act (soft below 8,4 °dH, medium 8,4 to 14 °dH, hard above that) and not a quality verdict — it indicates how much calcium and magnesium is dissolved in the water. Basis: 10.02.2026, retrieved on 11/07/2026.
- How much nitrate is in the drinking water in Husum, Schwesing, Simonsberg, Südermarsch und Spaltenhof?
- Stadtwerke Husum Netz GmbH publishes a nitrate value of 0,827 mg/l for the supply zone Wasserwerk Mildstedt, Pumpenhaus Werkausgang (Reinwasser, Husum 2). The statutory parametric value is 50 mg/l; the measured value represents 2 % of the parametric value. Basis: 10.02.2026, retrieved on 11/07/2026.
- Who supplies the drinking water in Husum, Schwesing, Simonsberg, Südermarsch und Spaltenhof?
- Stadtwerke Husum Netz GmbH. The values shown here come from the supply zone Wasserwerk Mildstedt, Pumpenhaus Werkausgang (Reinwasser, Husum 2) and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.
General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.