Skip to content
maunawai.info

Italy · Comune

Drinking water in Torno

One supply zone, published by Como Acqua S.r.l.. The values come from the publications of the Italian water suppliers (gestori), which D.Lgs. 18/2023 requires of them from 12 January 2026. Italian parametric values apply: trihalomethanes 30 instead of 50 µg/l, chromium 25 µg/l, uranium 30 instead of 10 µg/l; for hardness there is no maximum value, it is given in French degrees (°F).

Comune di Torno Fontana P.zza Caronti

Como Acqua S.r.l.
Water hardness
9 °dH
Key values Comune di Torno Fontana P.zza Caronti
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 6 mg/L 50 mg/l
12 %
Single value · Comune di Torno Fontana P.zza Caronti
Lead < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Single value · Comune di Torno Fontana P.zza Caronti
Escherichia coli (E. coli) < 1 MPN/100ml
below limit of quantification
0/100 ml Single value · Comune di Torno Fontana P.zza Caronti
Sulphate < 10 mg/L
below limit of quantification
250 mg/l
< 4 % *
Single value · Comune di Torno Fontana P.zza Caronti
Sodium < 15 mg/L
below limit of quantification
200 mg/l
< 8 % *
Single value · Comune di Torno Fontana P.zza Caronti

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Show all recorded parameters (44 — most recent value per parameter)

Microbiology (2)

Microbiology – Comune di Torno Fontana P.zza Caronti
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) < 1 MPN/100ml
below limit of quantification
0/100 ml Single value · Comune di Torno Fontana P.zza Caronti
Intestinal enterococci < 1 UFC/100 mL
below limit of quantification
0/100 ml Single value · Comune di Torno Fontana P.zza Caronti

Chemical parameters (21)

Chemical parameters – Comune di Torno Fontana P.zza Caronti
Parameter Value Parametric value Share of the parametric value Reference
1,2-dichloroethane < 0.2 µg/L
below limit of quantification
3 µg/l
< 7 % *
Single value · Comune di Torno Fontana P.zza Caronti
Antimony < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Single value · Comune di Torno Fontana P.zza Caronti
Arsenic < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Single value · Comune di Torno Fontana P.zza Caronti
Benzene < 0.2 µg/L
below limit of quantification
1 µg/l
< 20 % *
Single value · Comune di Torno Fontana P.zza Caronti
Boron < 0.05 mg/L
below limit of quantification
1.5 mg/l
< 3 % *
Single value · Comune di Torno Fontana P.zza Caronti
Cadmium < 1.0 µg/L
below limit of quantification
5 µg/l
< 20 % *
Single value · Comune di Torno Fontana P.zza Caronti
Chlorate 0.06 mg/L 0,25 — bzw. 0,70 bei Desinfektion mit Chlordioxid Single value · Comune di Torno Fontana P.zza Caronti
Chlorite < 0.05 mg/L
below limit of quantification
0,25 — bzw. 0,70 bei Desinfektion mit Chlordioxid Single value · Comune di Torno Fontana P.zza Caronti
Chromium < 5 µg/L
below limit of quantification
25 µg/l
< 20 % *
Single value · Comune di Torno Fontana P.zza Caronti
Copper < 0.05 mg/L
below limit of quantification
2 mg/l
< 3 % *
Single value · Comune di Torno Fontana P.zza Caronti
Fluoride < 0.20 mg/L
below limit of quantification
1.5 mg/l
< 13 % *
Single value · Comune di Torno Fontana P.zza Caronti
Lead < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Single value · Comune di Torno Fontana P.zza Caronti
Mercury < 0.25 µg/L
below limit of quantification
1 µg/l
< 25 % *
Single value · Comune di Torno Fontana P.zza Caronti
Nickel < 5 µg/L
below limit of quantification
20 µg/l
< 25 % *
Single value · Comune di Torno Fontana P.zza Caronti
Nitrate 6 mg/L 50 mg/l
12 %
Single value · Comune di Torno Fontana P.zza Caronti
Nitrite < 0.05 mg/L
below limit of quantification
0.5 mg/l
< 10 % *
Single value · Comune di Torno Fontana P.zza Caronti
Selenium < 5 µg/L
below limit of quantification
20 µg/l
< 25 % *
Single value · Comune di Torno Fontana P.zza Caronti
Tetrachloroethene and Trichloroethene (sum) < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Single value · Comune di Torno Fontana P.zza Caronti
Trihalomethanes — Total 6 µg/L 30 µg/l
20 %
Single value · Comune di Torno Fontana P.zza Caronti
Uranium < 1 µg/L
below limit of quantification
30 µg/l
< 3 % *
Single value · Comune di Torno Fontana P.zza Caronti
Vinyl chloride < 0.08 µg/L
below limit of quantification
0.5 µg/l
< 16 % *
Single value · Comune di Torno Fontana P.zza Caronti

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Indicator parameters (15)

Indicator parameters – Comune di Torno Fontana P.zza Caronti
Parameter Value Parametric value Share of the parametric value Reference
Aluminium 48 µg/L 0.2 mg/l
24 %
Single value · Comune di Torno Fontana P.zza Caronti
Ammonium < 0.02 mg/L
below limit of quantification
0.5 mg/l
< 4 % *
Single value · Comune di Torno Fontana P.zza Caronti
Chloride < 5 mg/L
below limit of quantification
250 mg/l
< 2 % *
Single value · Comune di Torno Fontana P.zza Caronti
Coliform bacteria < 1 MPN/100ml
below limit of quantification
0/100 ml Single value · Comune di Torno Fontana P.zza Caronti
Colony count 22 °C 23 UFC/1ml senza variazioni anomale Single value · Comune di Torno Fontana P.zza Caronti
Colour Accettabile accettabile per i consumatori, senza variazioni anomale Single value · Comune di Torno Fontana P.zza Caronti
Conductivity (25 °C) 275 µS/cm a 20°C 2,500 µS/cm Single value · Comune di Torno Fontana P.zza Caronti
Iron 41 µg/L 0.2 mg/l
21 %
Single value · Comune di Torno Fontana P.zza Caronti
Manganese < 5 µg/L
below limit of quantification
50 µg/l
< 10 % *
Single value · Comune di Torno Fontana P.zza Caronti
Odour Accettabile accettabile per i consumatori, senza variazioni anomale Single value · Comune di Torno Fontana P.zza Caronti
pH 8.01 Unità pH 6,5–9,5 Single value · Comune di Torno Fontana P.zza Caronti
Sodium < 15 mg/L
below limit of quantification
200 mg/l
< 8 % *
Single value · Comune di Torno Fontana P.zza Caronti
Sulphate < 10 mg/L
below limit of quantification
250 mg/l
< 4 % *
Single value · Comune di Torno Fontana P.zza Caronti
Taste Accettabile accettabile per i consumatori, senza variazioni anomale Single value · Comune di Torno Fontana P.zza Caronti
Turbidity 0.99 NTU accettabile per i consumatori, senza variazioni anomale Single value · Comune di Torno Fontana P.zza Caronti

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (6)

Further parameters – Comune di Torno Fontana P.zza Caronti
Parameter Value Parametric value Share of the parametric value Reference
Calcium 58 mg/L Single value · Comune di Torno Fontana P.zza Caronti
Dry residue 173 mg/L Single value · Comune di Torno Fontana P.zza Caronti
Magnesium < 5 mg/L
below limit of quantification
Single value · Comune di Torno Fontana P.zza Caronti
Potassium < 5 mg/L
below limit of quantification
Single value · Comune di Torno Fontana P.zza Caronti
Total hardness 16 °F Single value · Comune di Torno Fontana P.zza Caronti
Vanadium < 10 µg/L
below limit of quantification
0.14 mg/l
< 7 % *
Single value · Comune di Torno Fontana P.zza Caronti

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://comoacqua.it/qualita-acqua/ · 20 febbraio 2026 · Dati aggiornati al 20 febbraio 2026 · retrieved on 16/08/2026

How to read the share of the parametric value

12 % Share of the parametric value. The proportion of the permitted maximum that the measured value uses — here 12 %, so just over an eighth.
< 10 % * Below the limit of quantification. The substance was not detectable. The mark shows where the detection limit lies relative to the parametric value — the actual share of the parametric value is below that.

Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.

Legal basis: Art. 18 D.Lgs. 18/2023 as amended by D.Lgs. 102/2025 (transposition of EU Directive 2020/2184). The values are not official — the publication of the Gestore, to which every row links, remains authoritative. Assignment of the comune: information in the analysis document, resolved against the municipality list of ISTAT (territorial status 01.01.2026, CC BY 4.0).