Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.
Brunnen Hannslau
Stadtwerke Trostberg Wasserversorgung GmbHAssigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Nitrate | 15,0 mg/l | 50 mg/l | 30 % | Single value |
| Sulphate | 20,0 mg/l | 250 mg/l | 8 % | Single value |
| Sodium | 5,5 mg/l | 200 mg/l | 3 % | Single value |
Show all recorded parameters (12 — most recent value per parameter)
Chemical parameters (1)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Nitrate | 15,0 mg/l | 50 mg/l | 30 % | Single value |
Indicator parameters (8)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Chloride | 8,7 mg/l | 250 mg/l | 3 % | Single value |
| Colour | farblos Unit not stated in the document | 0.5 m⁻¹ | — | Single value |
| Odour | ohne Besonderheit | für den Verbraucher annehmbar | — | Single value |
| pH | 7,50 | 6,5–9,5 | — | Single value |
| Sodium | 5,5 mg/l | 200 mg/l | 3 % | Single value |
| Sulphate | 20,0 mg/l | 250 mg/l | 8 % | Single value |
| Temperature | 12,5 °C | — | — | Single value |
| Turbidity | klar Unit not stated in the document | 1 NTU | — | Single value |
Further parameters (3)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Calcium | 63,9 mg/l | — | — | Single value |
| Magnesium | 21,0 mg/l | — | — | Single value |
| Potassium | 1,0 mg/l | — | — | Single value |
Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.
Postcodes in this zone: 83308
Show 1 more supply zone
Zone Baumham, Tyrlaching, Michlbauer (OKZ 1230017101349)
ZV zur Wasserversorgung der Otting-Pallinger-GruppeAssigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Nitrate | 19 mg/l | 50 mg/l | 38 % | Single value |
| Lead | <0,001 mg/l below limit of quantification | 10 µg/l | < 10 % * | Single value |
| Escherichia coli (E. coli) | 0 KBE/100ml | 0/100 ml | — | Single value |
| Sulphate | 10 mg/l | 250 mg/l | 4 % | Single value |
| Sodium | 3,3 mg/l | 200 mg/l | 2 % | Single value |
* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.
Show all recorded parameters (60 — most recent value per parameter)
Microbiology (2)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Escherichia coli (E. coli) | 0 KBE/100ml | 0/100 ml | — | Single value |
| Intestinal enterococci | 0 KBE/100ml | 0/100 ml | — | Single value |
Chemical parameters (33)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| 1,2-dichloroethane | <0,0005 mg/l below limit of quantification | 3 µg/l | < 17 % * | Single value |
| Antimony | <0,0005 mg/l below limit of quantification | 5 µg/l | < 10 % * | Single value |
| Arsenic | <0,001 mg/l below limit of quantification | 10 µg/l | < 10 % * | Single value |
| Benzene | <0,0001 mg/l below limit of quantification | 1 µg/l | < 10 % * | Single value |
| Benzo(a)pyrene | <0,000002 mg/l below limit of quantification | 10 ng/l | < 20 % * | Single value |
| Benzo(b)fluoranthene | <0,000002 mg/l below limit of quantification | — | — | Single value |
| Benzo(ghi)perylene | <0,000002 mg/l below limit of quantification | — | — | Single value |
| Benzo(k)fluoranthene | <0,000002 mg/l below limit of quantification | — | — | Single value |
| Bisphenol A | <0,000050 (NWG) mg/l not detectable | 2.5 µg/l | — | Single value |
| Boron | <0,02 mg/l below limit of quantification | 1 mg/l | < 2 % * | Single value |
| Bromate | <0,0030 mg/l below limit of quantification | 10 µg/l | < 30 % * | Single value |
| Bromodichloromethane | <0,0002 mg/l below limit of quantification | — | — | Single value |
| Cadmium | <0,0003 mg/l below limit of quantification | 3 µg/l | < 10 % * | Single value |
| Chromium | <0,00050 mg/l below limit of quantification | 25 µg/l | < 2 % * | Single value |
| Copper | 0,005 mg/l | 2 mg/l | 0.3 % | Single value |
| Cyanide | <0,005 mg/l below limit of quantification | 50 µg/l | < 10 % * | Single value |
| Dibromochloromethane | <0,0002 mg/l below limit of quantification | — | — | Single value |
| Fluoride | 0,058 mg/l | 1.5 mg/l | 4 % | Single value |
| Lead | <0,001 mg/l below limit of quantification | 10 µg/l | < 10 % * | Single value |
| Mercury | <0,00010 mg/l below limit of quantification | 1 µg/l | < 10 % * | Single value |
| Nickel | <0,002 mg/l below limit of quantification | 20 µg/l | < 10 % * | Single value |
| Nitrate | 19 mg/l | 50 mg/l | 38 % | Single value |
| Nitrite | <0,02 mg/l below limit of quantification | 0.5 mg/l | < 4 % * | Single value |
| Polycyclic aromatic hydrocarbons | 0 mg/l | 0.1 µg/l | 0 % | Single value |
| Selenium | <0,0005 mg/l below limit of quantification | 10 µg/l | < 5 % * | Single value |
| Tetrachloroethene | <0,0001 mg/l below limit of quantification | — | — | Single value |
| Tetrachloroethene and Trichloroethene (sum) | 0 mg/l | 10 µg/l | 0 % | Single value |
| Tribromomethane (bromoform) | <0,0003 mg/l below limit of quantification | — | — | Single value |
| Trichloroethene | <0,0001 mg/l below limit of quantification | — | — | Single value |
| Trichloromethane (chloroform) | <0,0001 mg/l below limit of quantification | — | — | Single value |
| Trihalomethanes — Total | 0 mg/l | 50 µg/l | 0 % | Single value |
| Uranium | 0,0006 mg/l | 10 µg/l | 6 % | Single value |
| Vinyl chloride | <0,0001 mg/l below limit of quantification | 0.5 µg/l | < 20 % * | Single value |
* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.
Indicator parameters (16)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Aluminium | <0,020 mg/l below limit of quantification | 0.2 mg/l | < 10 % * | Single value |
| Ammonium | <0,01 mg/l below limit of quantification | 0.5 mg/l | < 2 % * | Single value |
| Calcite dissolution capacity | -32 mg/l | 5 mg/l CaCO3 | — | Single value |
| Chloride | 8,2 mg/l | 250 mg/l | 3 % | Single value |
| Coliform bacteria | 0 KBE/100ml | 0/100 ml | — | Single value |
| Colony count 22 °C | 1 KBE/ml | ohne anormale Veränderung | — | Single value |
| Colony count 36 °C | 2 KBE/ml | ohne anormale Veränderung | — | Single value |
| Conductivity (25 °C) | 624 µS/cm | 2,790 µS/cm | — | Single value |
| Iron | <0,005 mg/l below limit of quantification | 0.2 mg/l | < 3 % * | Single value |
| Manganese | <0,005 mg/l below limit of quantification | 50 µg/l | < 10 % * | Single value |
| pH | 7,37 | 6,5–9,5 | — | Single value |
| Sodium | 3,3 mg/l | 200 mg/l | 2 % | Single value |
| Sulphate | 10 mg/l | 250 mg/l | 4 % | Single value |
| Temperature | 11,7 °C | — | — | Single value |
| Total organic carbon (TOC) | <0,5 mg/l below limit of quantification | ohne anormale Veränderung | — | Single value |
| Turbidity | <0,05 NTU below limit of quantification | 1 NTU | — | Single value |
* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.
Further parameters (9)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Acid capacity to pH 4.3 | 6,24 mmol/l | — | — | Single value |
| Base capacity to pH 8.2 | 0,49 mmol/l | — | — | Single value |
| Calcium | 90,3 mg/l | — | — | Single value |
| Carbonate hardness | 17,3 °dH | — | — | Single value |
| Free carbon dioxide | 22 mg/l | — | — | Single value |
| Hardness range (WRMG) | hart | — | — | Single value |
| Magnesium | 26,7 mg/l | — | — | Single value |
| Potassium | 0,8 mg/l | — | — | Single value |
| Total hardness | 3,35 mmol/l | — | — | Single value |
Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.
Postcodes in this zone: 83308
Frequently asked questions about drinking water in Trostberg
- How much nitrate is in the drinking water in Trostberg?
- Stadtwerke Trostberg Wasserversorgung GmbH publishes a nitrate value of 15,0 mg/l for the supply zone Brunnen Hannslau. The statutory parametric value is 50 mg/l; the measured value represents 30 % of the parametric value. Basis: Publication by the water supplier, retrieved on 11/07/2026.
- Who supplies the drinking water in Trostberg?
- Stadtwerke Trostberg Wasserversorgung GmbH. The values shown here come from the supply zone Brunnen Hannslau and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.