Skip to content
maunawai.info

Drinking water in Sternberg, Dabel u.a.

4 supply zones — values can differ depending on the district. Below is the zone with the most documented parameters, the others collapsed underneath. To determine the exact match, look up the postcode.

How to read the share of the parametric value

12 % Share of the parametric value. The proportion of the permitted maximum that the measured value uses — here 12 %, so just over an eighth.
< 10 % * Below the limit of quantification. The substance was not detectable. The mark shows where the detection limit lies relative to the parametric value — the actual share of the parametric value is below that.

Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.

Wasserwerk Klein Görnow

Stadtwerke Sternberg

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

Water hardness
10,6 / 1,89 °dH/mmol/l
Hardness range hart
Key values Wasserwerk Klein Görnow
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 0,87 mg/l 50 mg/l
2 %
Single value · Wasserwerk Klein Görnow
Escherichia coli (E. coli) 0 n/100 ml 0/100 ml Single value · Wasserwerk Klein Görnow
Sulphate 54,9 mg/l 250 mg/l
22 %
Single value · Wasserwerk Klein Görnow
Sodium 12,3 mg/l 200 mg/l
6 %
Single value · Wasserwerk Klein Görnow
Show all recorded parameters (29 — most recent value per parameter)

Microbiology (2)

Microbiology – Wasserwerk Klein Görnow
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) 0 n/100 ml 0/100 ml Single value · Wasserwerk Klein Görnow
Intestinal enterococci 0 n/100 ml 0/100 ml Single value · Wasserwerk Klein Görnow

Chemical parameters (5)

Chemical parameters – Wasserwerk Klein Görnow
Parameter Value Parametric value Share of the parametric value Reference
Copper <0,01 mg/l
below limit of quantification
2 mg/l
< 0.5 % *
Single value · Wasserwerk Klein Görnow
Fluoride 0,1 mg/l 1.5 mg/l
7 %
Single value · Wasserwerk Klein Görnow
Nitrate 0,87 mg/l 50 mg/l
2 %
Single value · Wasserwerk Klein Görnow
Nitrite <0,01 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Single value · Wasserwerk Klein Görnow
Uranium <0,0005 mg/l
below limit of quantification
10 µg/l
< 5 % *
Single value · Wasserwerk Klein Görnow

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Indicator parameters (14)

Indicator parameters – Wasserwerk Klein Görnow
Parameter Value Parametric value Share of the parametric value Reference
Ammonium < 0,1 mg/l
below limit of quantification
0.5 mg/l
< 20 % *
Single value · Wasserwerk Klein Görnow
Chloride 14,4 mg/l 250 mg/l
6 %
Single value · Wasserwerk Klein Görnow
Coliform bacteria 0 n/100 ml 0/100 ml Single value · Wasserwerk Klein Görnow
Colony count 22 °C 0 n/ml ohne anormale Veränderung Single value · Wasserwerk Klein Görnow
Colony count 36 °C 0 n/ml ohne anormale Veränderung Single value · Wasserwerk Klein Görnow
Conductivity (25 °C) 465 µS/cm 2,790 µS/cm Single value · Wasserwerk Klein Görnow
Iron < 0,02 mg/l
below limit of quantification
0.2 mg/l
< 10 % *
Single value · Wasserwerk Klein Görnow
Manganese < 0,005 mg/l
below limit of quantification
50 µg/l
< 10 % *
Single value · Wasserwerk Klein Görnow
pH 7,68 6,5–9,5 Single value · Wasserwerk Klein Görnow
Sodium 12,3 mg/l 200 mg/l
6 %
Single value · Wasserwerk Klein Görnow
Sulphate 54,9 mg/l 250 mg/l
22 %
Single value · Wasserwerk Klein Görnow
Temperature 11 °C Single value · Wasserwerk Klein Görnow
Total organic carbon (TOC) 2,4 mg/l ohne anormale Veränderung Single value · Wasserwerk Klein Görnow
Turbidity 0,31 NTU 1 NTU Single value · Wasserwerk Klein Görnow

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (8)

Further parameters – Wasserwerk Klein Görnow
Parameter Value Parametric value Share of the parametric value Reference
Acid capacity to pH 4.3 2,67 mmol/l Single value · Wasserwerk Klein Görnow
Base capacity to pH 8.2 0,06 mmol/l Single value · Wasserwerk Klein Görnow
Calcium 68,1 mg/l Single value · Wasserwerk Klein Görnow
Hardness range (WRMG) hart Single value · Wasserwerk Klein Görnow
Magnesium 4,66 mg/l Single value · Wasserwerk Klein Görnow
Oxygen 6,9 mg/l Single value · Wasserwerk Klein Görnow
Potassium 0,83 mg/l Single value · Wasserwerk Klein Görnow
Total hardness 10,6 / 1,89 °dH/mmol/l Single value · Wasserwerk Klein Görnow

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Postcodes in this zone: 19406

Show 3 more supply zones

Wasserwerk Kukuk

Stadtwerke Sternberg

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

Water hardness
21,7 / 3,88 °dH/mmol/l
Hardness range hart
Key values Wasserwerk Kukuk
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 0,27 mg/l 50 mg/l
0.5 %
Single value · Wasserwerk Kukuk
Escherichia coli (E. coli) 0 n/100 ml 0/100 ml Single value · Wasserwerk Kukuk
Sulphate 130 mg/l 250 mg/l
52 %
Single value · Wasserwerk Kukuk
Sodium 9,68 mg/l 200 mg/l
5 %
Single value · Wasserwerk Kukuk
Show all recorded parameters (29 — most recent value per parameter)

Microbiology (2)

Microbiology – Wasserwerk Kukuk
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) 0 n/100 ml 0/100 ml Single value · Wasserwerk Kukuk
Intestinal enterococci 0 n/100 ml 0/100 ml Single value · Wasserwerk Kukuk

Chemical parameters (5)

Chemical parameters – Wasserwerk Kukuk
Parameter Value Parametric value Share of the parametric value Reference
Copper <0,01 mg/l
below limit of quantification
2 mg/l
< 0.5 % *
Single value · Wasserwerk Kukuk
Fluoride 0,25 mg/l 1.5 mg/l
17 %
Single value · Wasserwerk Kukuk
Nitrate 0,27 mg/l 50 mg/l
0.5 %
Single value · Wasserwerk Kukuk
Nitrite <0,01 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Single value · Wasserwerk Kukuk
Uranium <0,0005 mg/l
below limit of quantification
10 µg/l
< 5 % *
Single value · Wasserwerk Kukuk

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Indicator parameters (14)

Indicator parameters – Wasserwerk Kukuk
Parameter Value Parametric value Share of the parametric value Reference
Ammonium < 0,1 mg/l
below limit of quantification
0.5 mg/l
< 20 % *
Single value · Wasserwerk Kukuk
Chloride 33,7 mg/l 250 mg/l
13 %
Single value · Wasserwerk Kukuk
Coliform bacteria 0 n/100 ml 0/100 ml Single value · Wasserwerk Kukuk
Colony count 22 °C 0 n/ml ohne anormale Veränderung Single value · Wasserwerk Kukuk
Colony count 36 °C 0 n/ml ohne anormale Veränderung Single value · Wasserwerk Kukuk
Conductivity (25 °C) 700 µS/cm 2,790 µS/cm Single value · Wasserwerk Kukuk
Iron < 0,03 mg/l
below limit of quantification
0.2 mg/l
< 15 % *
Single value · Wasserwerk Kukuk
Manganese < 0,005 mg/l
below limit of quantification
50 µg/l
< 10 % *
Single value · Wasserwerk Kukuk
pH 7,44 6,5–9,5 Single value · Wasserwerk Kukuk
Sodium 9,68 mg/l 200 mg/l
5 %
Single value · Wasserwerk Kukuk
Sulphate 130 mg/l 250 mg/l
52 %
Single value · Wasserwerk Kukuk
Temperature 9,4 °C Single value · Wasserwerk Kukuk
Total organic carbon (TOC) 1,0 mg/l ohne anormale Veränderung Single value · Wasserwerk Kukuk
Turbidity 0,1 NTU 1 NTU Single value · Wasserwerk Kukuk

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (8)

Further parameters – Wasserwerk Kukuk
Parameter Value Parametric value Share of the parametric value Reference
Acid capacity to pH 4.3 4,41 mmol/l Single value · Wasserwerk Kukuk
Base capacity to pH 8.2 0,46 mmol/l Single value · Wasserwerk Kukuk
Calcium 128 mg/l Single value · Wasserwerk Kukuk
Hardness range (WRMG) hart Single value · Wasserwerk Kukuk
Magnesium 16,5 mg/l Single value · Wasserwerk Kukuk
Oxygen 6,5 mg/l Single value · Wasserwerk Kukuk
Potassium 1,33 mg/l Single value · Wasserwerk Kukuk
Total hardness 21,7 / 3,88 °dH/mmol/l Single value · Wasserwerk Kukuk

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Postcodes in this zone: 19406

Wasserwerk Sternberg

Stadtwerke Sternberg

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

Water hardness
16,1 / 2,87 °dH/mmol/l
Hardness range hart
Key values Wasserwerk Sternberg
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 3,24 mg/l 50 mg/l
6 %
Single value · Wasserwerk Sternberg
Escherichia coli (E. coli) 0 n/100 ml 0/100 ml Single value · Wasserwerk Sternberg
Sulphate 27,4 mg/l 250 mg/l
11 %
Single value · Wasserwerk Sternberg
Sodium 21,2 mg/l 200 mg/l
11 %
Single value · Wasserwerk Sternberg
Show all recorded parameters (29 — most recent value per parameter)

Microbiology (2)

Microbiology – Wasserwerk Sternberg
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) 0 n/100 ml 0/100 ml Single value · Wasserwerk Sternberg
Intestinal enterococci 0 n/100 ml 0/100 ml Single value · Wasserwerk Sternberg

Chemical parameters (5)

Chemical parameters – Wasserwerk Sternberg
Parameter Value Parametric value Share of the parametric value Reference
Copper <0,01 mg/l
below limit of quantification
2 mg/l
< 0.5 % *
Single value · Wasserwerk Sternberg
Fluoride 0,21 mg/l 1.5 mg/l
14 %
Single value · Wasserwerk Sternberg
Nitrate 3,24 mg/l 50 mg/l
6 %
Single value · Wasserwerk Sternberg
Nitrite <0,01 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Single value · Wasserwerk Sternberg
Uranium <0,0005 mg/l
below limit of quantification
10 µg/l
< 5 % *
Single value · Wasserwerk Sternberg

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Indicator parameters (14)

Indicator parameters – Wasserwerk Sternberg
Parameter Value Parametric value Share of the parametric value Reference
Ammonium < 0,1 mg/l
below limit of quantification
0.5 mg/l
< 20 % *
Single value · Wasserwerk Sternberg
Chloride 40,8 mg/l 250 mg/l
16 %
Single value · Wasserwerk Sternberg
Coliform bacteria 0 n/100 ml 0/100 ml Single value · Wasserwerk Sternberg
Colony count 22 °C 0 n/ml ohne anormale Veränderung Single value · Wasserwerk Sternberg
Colony count 36 °C 0 n/ml ohne anormale Veränderung Single value · Wasserwerk Sternberg
Conductivity (25 °C) 577 µS/cm 2,790 µS/cm Single value · Wasserwerk Sternberg
Iron < 0,03 mg/l
below limit of quantification
0.2 mg/l
< 15 % *
Single value · Wasserwerk Sternberg
Manganese < 0,005 mg/l
below limit of quantification
50 µg/l
< 10 % *
Single value · Wasserwerk Sternberg
pH 7,16 6,5–9,5 Single value · Wasserwerk Sternberg
Sodium 21,2 mg/l 200 mg/l
11 %
Single value · Wasserwerk Sternberg
Sulphate 27,4 mg/l 250 mg/l
11 %
Single value · Wasserwerk Sternberg
Temperature 11 °C Single value · Wasserwerk Sternberg
Total organic carbon (TOC) 2,1 mg/l ohne anormale Veränderung Single value · Wasserwerk Sternberg
Turbidity 0,49 NTU 1 NTU Single value · Wasserwerk Sternberg

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (8)

Further parameters – Wasserwerk Sternberg
Parameter Value Parametric value Share of the parametric value Reference
Acid capacity to pH 4.3 6,07 mmol/l Single value · Wasserwerk Sternberg
Base capacity to pH 8.2 0,51 mmol/l Single value · Wasserwerk Sternberg
Calcium 91,4 mg/l Single value · Wasserwerk Sternberg
Hardness range (WRMG) hart Single value · Wasserwerk Sternberg
Magnesium 14,3 mg/l Single value · Wasserwerk Sternberg
Oxygen 6,4 mg/l Single value · Wasserwerk Sternberg
Potassium 3,54 mg/l Single value · Wasserwerk Sternberg
Total hardness 16,1 / 2,87 °dH/mmol/l Single value · Wasserwerk Sternberg

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Postcodes in this zone: 19406

Wasserwerk Sülten

Stadtwerke Sternberg

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

Water hardness
15 / 2,68 °dH/mmol/l
Hardness range hart
Key values Wasserwerk Sülten
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 0,98 mg/l 50 mg/l
2 %
Single value · Wasserwerk Sülten
Escherichia coli (E. coli) 0 n/100 ml 0/100 ml Single value · Wasserwerk Sülten
Sulphate 44,9 mg/l 250 mg/l
18 %
Single value · Wasserwerk Sülten
Sodium 17,3 mg/l 200 mg/l
9 %
Single value · Wasserwerk Sülten
Show all recorded parameters (29 — most recent value per parameter)

Microbiology (2)

Microbiology – Wasserwerk Sülten
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) 0 n/100 ml 0/100 ml Single value · Wasserwerk Sülten
Intestinal enterococci 0 n/100 ml 0/100 ml Single value · Wasserwerk Sülten

Chemical parameters (5)

Chemical parameters – Wasserwerk Sülten
Parameter Value Parametric value Share of the parametric value Reference
Copper <0,01 mg/l
below limit of quantification
2 mg/l
< 0.5 % *
Single value · Wasserwerk Sülten
Fluoride 0,23 mg/l 1.5 mg/l
15 %
Single value · Wasserwerk Sülten
Nitrate 0,98 mg/l 50 mg/l
2 %
Single value · Wasserwerk Sülten
Nitrite <0,01 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Single value · Wasserwerk Sülten
Uranium <0,0005 mg/l
below limit of quantification
10 µg/l
< 5 % *
Single value · Wasserwerk Sülten

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Indicator parameters (14)

Indicator parameters – Wasserwerk Sülten
Parameter Value Parametric value Share of the parametric value Reference
Ammonium < 0,1 mg/l
below limit of quantification
0.5 mg/l
< 20 % *
Single value · Wasserwerk Sülten
Chloride 21,8 mg/l 250 mg/l
9 %
Single value · Wasserwerk Sülten
Coliform bacteria 0 n/100 ml 0/100 ml Single value · Wasserwerk Sülten
Colony count 22 °C 0 n/ml ohne anormale Veränderung Single value · Wasserwerk Sülten
Colony count 36 °C 0 n/ml ohne anormale Veränderung Single value · Wasserwerk Sülten
Conductivity (25 °C) 526 µS/cm 2,790 µS/cm Single value · Wasserwerk Sülten
Iron < 0,02 mg/l
below limit of quantification
0.2 mg/l
< 10 % *
Single value · Wasserwerk Sülten
Manganese < 0,005 mg/l
below limit of quantification
50 µg/l
< 10 % *
Single value · Wasserwerk Sülten
pH 7,5 6,5–9,5 Single value · Wasserwerk Sülten
Sodium 17,3 mg/l 200 mg/l
9 %
Single value · Wasserwerk Sülten
Sulphate 44,9 mg/l 250 mg/l
18 %
Single value · Wasserwerk Sülten
Temperature 9,2 °C Single value · Wasserwerk Sülten
Total organic carbon (TOC) 1,3 mg/l ohne anormale Veränderung Single value · Wasserwerk Sülten
Turbidity 0,1 NTU 1 NTU Single value · Wasserwerk Sülten

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (8)

Further parameters – Wasserwerk Sülten
Parameter Value Parametric value Share of the parametric value Reference
Acid capacity to pH 4.3 3,43 mmol/l Single value · Wasserwerk Sülten
Base capacity to pH 8.2 0,37 mmol/l Single value · Wasserwerk Sülten
Calcium 85,6 mg/l Single value · Wasserwerk Sülten
Hardness range (WRMG) hart Single value · Wasserwerk Sülten
Magnesium 13,2 mg/l Single value · Wasserwerk Sülten
Oxygen 10,5 mg/l Single value · Wasserwerk Sülten
Potassium 2,68 mg/l Single value · Wasserwerk Sülten
Total hardness 15 / 2,68 °dH/mmol/l Single value · Wasserwerk Sülten

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Postcodes in this zone: 19406

Frequently asked questions about drinking water in Sternberg, Dabel u.a.

How hard is the water in Sternberg, Dabel u.a.?
Stadtwerke Sternberg publishes the hardness range hart for the supply zone Wasserwerk Klein Görnow. The hardness range is a classification under the German Detergents and Cleaning Products Act (soft below 8,4 °dH, medium 8,4 to 14 °dH, hard above that) and not a quality verdict — it indicates how much calcium and magnesium is dissolved in the water. Basis: Publication by the water supplier, retrieved on 18/08/2026.
How much nitrate is in the drinking water in Sternberg, Dabel u.a.?
Stadtwerke Sternberg publishes a nitrate value of 0,87 mg/l for the supply zone Wasserwerk Klein Görnow. The statutory parametric value is 50 mg/l; the measured value represents 2 % of the parametric value. Basis: Publication by the water supplier, retrieved on 18/08/2026.
Who supplies the drinking water in Sternberg, Dabel u.a.?
Stadtwerke Sternberg. The values shown here come from the supply zone Wasserwerk Klein Görnow and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.

General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.