Skip to content
maunawai.info

Drinking water in Salzkotten

One supply zone, water supplier: Stadtwerke Salzkotten.

How to read the share of the parametric value

12 % Share of the parametric value. The proportion of the permitted maximum that the measured value uses — here 12 %, so just over an eighth.
< 10 % * Below the limit of quantification. The substance was not detectable. The mark shows where the detection limit lies relative to the parametric value — the actual share of the parametric value is below that.

Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.

Ablauf Hochbehälter, Hochbehälter Salzkotten, Wewelsburger Straße / Mackeloh, 33154 Salzkotten

Stadtwerke Salzkotten

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

Water hardness
10.3 °dH
Hardness range mittel
Key values Ablauf Hochbehälter, Hochbehälter Salzkotten, Wewelsburger Straße / Mackeloh, 33154 Salzkotten
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 20 mg/l 50 mg/l
40 %
Single value
Lead <0,0010 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value
Sulphate 18 mg/l 250 mg/l
7 %
Single value
Sodium 74,8 mg/l 200 mg/l
37 %
Single value

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Show all recorded parameters (55 — most recent value per parameter)

Chemical parameters (34)

Chemical parameters – Ablauf Hochbehälter, Hochbehälter Salzkotten, Wewelsburger Straße / Mackeloh, 33154 Salzkotten
Parameter Value Parametric value Share of the parametric value Reference
1,2-dichloroethane <0,5 µg/l
below limit of quantification
3 µg/l
< 17 % *
Single value
Antimony <0,0010 mg/l
below limit of quantification
5 µg/l
< 20 % *
Single value
Arsenic <0,0010 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value
Benzene <0,3 µg/l
below limit of quantification
1 µg/l
< 30 % *
Single value
Benzo(a)pyrene <0,0030 µg/l
below limit of quantification
10 ng/l
< 30 % *
Single value
Benzo(b)fluoranthene <0,004 µg/l
below limit of quantification
Single value
Benzo(ghi)perylene <0,003 µg/l
below limit of quantification
Single value
Benzo(k)fluoranthene <0,003 µg/l
below limit of quantification
Single value
Bisphenol A <0,0001 mg/l
below limit of quantification
2.5 µg/l
< 4 % *
Single value
Boron 0,0297 mg/l 1 mg/l
3 %
Single value
Bromate <0,003 mg/l
below limit of quantification
10 µg/l
< 30 % *
Single value
Bromodichloromethane <0,5 µg/l
below limit of quantification
Single value
Cadmium <0,00010 mg/l
below limit of quantification
3 µg/l
< 3 % *
Single value
Chromium 0,00010 mg/l 25 µg/l
0.4 %
Single value
Copper <0,0100 mg/l
below limit of quantification
2 mg/l
< 0.5 % *
Single value
Cyanide <0,005 mg/l
below limit of quantification
50 µg/l
< 10 % *
Single value
Dibromochloromethane <0,5 µg/l
below limit of quantification
Single value
Fluoride <0,1 mg/l
below limit of quantification
1.5 mg/l
< 7 % *
Single value
Indeno(1,2,3-cd)pyrene <0,004 µg/l
below limit of quantification
Single value
Lead <0,0010 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value
Mercury <0,0001 mg/l
below limit of quantification
1 µg/l
< 10 % *
Single value
Nickel <0,0010 mg/l
below limit of quantification
20 µg/l
< 5 % *
Single value
Nitrate 20 mg/l 50 mg/l
40 %
Single value
Nitrite <0,005 mg/l
below limit of quantification
0.5 mg/l
< 1 % *
Single value
Polycyclic aromatic hydrocarbons <0,030 µg/l
below limit of quantification
0.1 µg/l
< 30 % *
Single value
Selenium <0,0010 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value
Tetrachloroethene <0,5 µg/l
below limit of quantification
Single value
Tetrachloroethene and Trichloroethene (sum) <0,5 µg/l
below limit of quantification
10 µg/l
< 5 % *
Single value
Tribromomethane (bromoform) <1,00 µg/l
below limit of quantification
Single value
Trichloroethene <0,5 µg/l
below limit of quantification
Single value
Trichloromethane (chloroform) <0,5 µg/l
below limit of quantification
Single value
Trihalomethanes — Total <0,0005 mg/l
below limit of quantification
50 µg/l
< 1 % *
Single value
Uranium 0,00018 mg/l 10 µg/l
2 %
Single value
Vinyl chloride <0,5 µg/l
below limit of quantification
0.5 µg/l
< 100 % *
Single value

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Indicator parameters (15)

Indicator parameters – Ablauf Hochbehälter, Hochbehälter Salzkotten, Wewelsburger Straße / Mackeloh, 33154 Salzkotten
Parameter Value Parametric value Share of the parametric value Reference
Aluminium <0,0050 mg/l
below limit of quantification
0.2 mg/l
< 3 % *
Single value
Ammonium <0,05 mg/l
below limit of quantification
0.5 mg/l
< 10 % *
Single value
Calcite dissolution capacity -12,3 mg/l 5 mg/l CaCO3 Single value
Chloride 91 mg/l 250 mg/l
36 %
Single value
Colour <0,1 1/m
below limit of quantification
0.5 m⁻¹ Single value
Conductivity (25 °C) 688 µS/cm 2,790 µS/cm Single value
Iron <0,010 mg/l
below limit of quantification
0.2 mg/l
< 5 % *
Single value
Manganese <0,0050 mg/l
below limit of quantification
50 µg/l
< 10 % *
Single value
Oxidisability <0,50 mg/l
below limit of quantification
5 mg/l O2 Single value
pH 7,78 6,5–9,5 Single value
Sodium 74,8 mg/l 200 mg/l
37 %
Single value
Sulphate 18 mg/l 250 mg/l
7 %
Single value
Temperature 10,3 °C Single value
Total organic carbon (TOC) 1,1 mg/l ohne anormale Veränderung Single value
Turbidity <0,05 NTU
below limit of quantification
1 NTU Single value

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (6)

Further parameters – Ablauf Hochbehälter, Hochbehälter Salzkotten, Wewelsburger Straße / Mackeloh, 33154 Salzkotten
Parameter Value Parametric value Share of the parametric value Reference
Acid capacity to pH 4.3 3,99 mmol/l Single value
Calcium 69,7 mg/l Single value
Hardness range (WRMG) mittel Single value
Magnesium 2,38 mg/l Single value
Potassium 2,96 mg/l Single value
Total hardness 10,3 °dH Single value

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Postcodes in this zone: 33154

Frequently asked questions about drinking water in Salzkotten

How hard is the water in Salzkotten?
Stadtwerke Salzkotten publishes a total hardness of 10.3 °dH for the supply zone Ablauf Hochbehälter, Hochbehälter Salzkotten, Wewelsburger Straße / Mackeloh, 33154 Salzkotten (hardness range mittel). The hardness range is a classification under the German Detergents and Cleaning Products Act (soft below 8,4 °dH, medium 8,4 to 14 °dH, hard above that) and not a quality verdict — it indicates how much calcium and magnesium is dissolved in the water. Basis: 20.02.2026, retrieved on 11/07/2026.
How much nitrate is in the drinking water in Salzkotten?
Stadtwerke Salzkotten publishes a nitrate value of 20 mg/l for the supply zone Ablauf Hochbehälter, Hochbehälter Salzkotten, Wewelsburger Straße / Mackeloh, 33154 Salzkotten. The statutory parametric value is 50 mg/l; the measured value represents 40 % of the parametric value. Basis: 20.02.2026, retrieved on 11/07/2026.
Who supplies the drinking water in Salzkotten?
Stadtwerke Salzkotten. The values shown here come from the supply zone Ablauf Hochbehälter, Hochbehälter Salzkotten, Wewelsburger Straße / Mackeloh, 33154 Salzkotten and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.

General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.