Skip to content
maunawai.info

Drinking water in Rüdesheim

One supply zone, water supplier: TWIST RLP - Stromberger Str. (WW), TW.

How to read the share of the parametric value

12 % Share of the parametric value. The proportion of the permitted maximum that the measured value uses — here 12 %, so just over an eighth.
< 10 % * Below the limit of quantification. The substance was not detectable. The mark shows where the detection limit lies relative to the parametric value — the actual share of the parametric value is below that.

Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.

Stromberger Str. (WW), TW

TWIST RLP - Stromberger Str. (WW), TW

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

No date is given for these values. The water supplier publishes the analysis without a sampling date and without a report date. When the water was examined is not apparent from the source — we do not add a date and we do not estimate one. What is stated is therefore only when we retrieved the document.

Water hardness
11.9 °dH
Hardness range medium
Key values Stromberger Str. (WW), TW
Parameter Value Parametric value Share of the parametric value Reference
Sum of PFAS 0.023 µg/L 0.1 µg/l
23 %
Mean · Stromberger Str. (WW), TW
Nitrate 23 mg/L 50 mg/l
46 %
Mean · Stromberger Str. (WW), TW
Lead < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Mean · Stromberger Str. (WW), TW
Escherichia coli (E. coli) 0 Anzahl/100ml 0/100 ml Mean · Stromberger Str. (WW), TW
Sulphate 33 mg/L 250 mg/l
13 %
Mean · Stromberger Str. (WW), TW
Sodium 28.1 mg/L 200 mg/l
14 %
Mean · Stromberger Str. (WW), TW

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Show all recorded parameters (30 — most recent value per parameter)

Microbiology (1)

Microbiology – Stromberger Str. (WW), TW
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) 0 Anzahl/100ml 0/100 ml Mean · Stromberger Str. (WW), TW

Chemical parameters (14)

Chemical parameters – Stromberger Str. (WW), TW
Parameter Value Parametric value Share of the parametric value Reference
Antimony < 1 µg/L
below limit of quantification
5 µg/l
< 20 % *
Mean · Stromberger Str. (WW), TW
Arsenic < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Mean · Stromberger Str. (WW), TW
Boron 0.1 mg/L 1 mg/l
10 %
Mean · Stromberger Str. (WW), TW
Cadmium < 0.2 µg/L
below limit of quantification
3 µg/l
< 7 % *
Mean · Stromberger Str. (WW), TW
Copper 0.008 mg/L 2 mg/l
0.4 %
Mean · Stromberger Str. (WW), TW
Cyanide < 0.003 mg/L
below limit of quantification
50 µg/l
< 6 % *
Mean · Stromberger Str. (WW), TW
Fluoride 0.05 mg/L 1.5 mg/l
3 %
Mean · Stromberger Str. (WW), TW
Lead < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Mean · Stromberger Str. (WW), TW
Mercury < 0.1 µg/L
below limit of quantification
1 µg/l
< 10 % *
Mean · Stromberger Str. (WW), TW
Nickel < 5 µg/L
below limit of quantification
20 µg/l
< 25 % *
Mean · Stromberger Str. (WW), TW
Nitrate 23 mg/L 50 mg/l
46 %
Mean · Stromberger Str. (WW), TW
Nitrite < 0.005 mg/L
below limit of quantification
0.5 mg/l
< 1 % *
Mean · Stromberger Str. (WW), TW
Selenium < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Mean · Stromberger Str. (WW), TW
Uranium 3.2 µg/L 10 µg/l
32 %
Mean · Stromberger Str. (WW), TW

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

PFAS (1)

PFAS – Stromberger Str. (WW), TW
Parameter Value Parametric value Share of the parametric value Reference
Sum of PFAS 0.023 µg/L 0.1 µg/l
23 %
Mean · Stromberger Str. (WW), TW

Indicator parameters (10)

Indicator parameters – Stromberger Str. (WW), TW
Parameter Value Parametric value Share of the parametric value Reference
Aluminium < 0.005 mg/L
below limit of quantification
0.2 mg/l
< 3 % *
Mean · Stromberger Str. (WW), TW
Ammonium 0.1 mg/L 0.5 mg/l
20 %
Mean · Stromberger Str. (WW), TW
Chloride 45 mg/L 250 mg/l
18 %
Mean · Stromberger Str. (WW), TW
Coliform bacteria 0 Anzahl/100ml 0/100 ml Mean · Stromberger Str. (WW), TW
Iron < 0.05 mg/L
below limit of quantification
0.2 mg/l
< 25 % *
Mean · Stromberger Str. (WW), TW
Manganese < 0.01 mg/L
below limit of quantification
50 µg/l
< 20 % *
Mean · Stromberger Str. (WW), TW
pH 7.89 - 6,5–9,5 Mean · Stromberger Str. (WW), TW
Sodium 28.1 mg/L 200 mg/l
14 %
Mean · Stromberger Str. (WW), TW
Sulphate 33 mg/L 250 mg/l
13 %
Mean · Stromberger Str. (WW), TW
Temperature 11.5 °C Mean · Stromberger Str. (WW), TW

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (4)

Further parameters – Stromberger Str. (WW), TW
Parameter Value Parametric value Share of the parametric value Reference
Calcium 56 mg/L Mean · Stromberger Str. (WW), TW
Magnesium 16.2 mg/L Mean · Stromberger Str. (WW), TW
Potassium 3 mg/L Mean · Stromberger Str. (WW), TW
Total hardness 2.13 mmol/l Mean · Stromberger Str. (WW), TW

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://geodaten-wasser.rlp-umwelt.de/twist/2549695058/trinkwasserqualitaet · Mittelwerte · retrieved on 13/07/2026

Postcodes in this zone: 55593

Frequently asked questions about drinking water in Rüdesheim

How hard is the water in Rüdesheim?
TWIST RLP - Stromberger Str. (WW), TW publishes a total hardness of 2.13 mmol/l for the supply zone Stromberger Str. (WW), TW — that corresponds to 11.9 °dH. The hardness range is a classification under the German Detergents and Cleaning Products Act (soft below 8,4 °dH, medium 8,4 to 14 °dH, hard above that) and not a quality verdict — it indicates how much calcium and magnesium is dissolved in the water. Basis: Publication by the water supplier, retrieved on 13/07/2026.
How much nitrate is in the drinking water in Rüdesheim?
TWIST RLP - Stromberger Str. (WW), TW publishes a nitrate value of 23 mg/L for the supply zone Stromberger Str. (WW), TW. The statutory parametric value is 50 mg/l; the measured value represents 46 % of the parametric value. Basis: Publication by the water supplier, retrieved on 13/07/2026.
Are PFAS detectable in the drinking water in Rüdesheim?
TWIST RLP - Stromberger Str. (WW), TW publishes for the supply zone Stromberger Str. (WW), TW a sum value PFAS-20 of 0.023 µg/L. The statutory parametric value is 0.1 µg/l; the measured value represents 23 % of the parametric value. For the sum of the 20 individual substances, this parametric value has applied since 12/01/2026. Basis: Publication by the water supplier, retrieved on 13/07/2026.
Who supplies the drinking water in Rüdesheim?
TWIST RLP - Stromberger Str. (WW), TW. The values shown here come from the supply zone Stromberger Str. (WW), TW and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.

General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.