Skip to content
maunawai.info

Drinking water in Nußdorf am Haunsberg, Obertrum am See, Seekirchen am Wallersee

One supply zone, water supplier: Marktgemeinde Obertrum am See.

How to read the share of the parametric value

12 % Share of the parametric value. The proportion of the permitted maximum that the measured value uses — here 12 %, so just over an eighth.
< 10 % * Below the limit of quantification. The substance was not detectable. The mark shows where the detection limit lies relative to the parametric value — the actual share of the parametric value is below that.

Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.

GD Obertrum, TWA; Spielberggrabenquellen - PN Spielberggraben, Zulauf QSS oro re

Marktgemeinde Obertrum am See

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

Water hardness
16.6 °dH
Hardness range hard
Key values GD Obertrum, TWA; Spielberggrabenquellen - PN Spielberggraben, Zulauf QSS oro re
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 3,9 mg/l 50 mg/l
8 %
Single value
Escherichia coli (E. coli) n.n. KBE/100ml
not detectable
0/100 ml Single value
Sulphate 8,1 mg/l 250 mg/l
3 %
Single value
Sodium 6,4 mg/l 200 mg/l
3 %
Single value
Show all recorded parameters (19 — most recent value per parameter)

Microbiology (2)

Microbiology – GD Obertrum, TWA; Spielberggrabenquellen - PN Spielberggraben, Zulauf QSS oro re
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) n.n. KBE/100ml
not detectable
0/100 ml Single value
Intestinal enterococci n.n. KBE/100ml
not detectable
0/100 ml Single value

Chemical parameters (2)

Chemical parameters – GD Obertrum, TWA; Spielberggrabenquellen - PN Spielberggraben, Zulauf QSS oro re
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 3,9 mg/l 50 mg/l
8 %
Single value
Nitrite < 0,003 mg/l
below limit of quantification
0.1 mg/l
< 3 % *
Single value

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Indicator parameters (9)

Indicator parameters – GD Obertrum, TWA; Spielberggrabenquellen - PN Spielberggraben, Zulauf QSS oro re
Parameter Value Parametric value Share of the parametric value Reference
Ammonium < 0,02 mg/l
below limit of quantification
0.5 mg/l
< 4 % *
Single value
Chloride 8,1 mg/l 200 mg/l
4 %
Single value
Coliform bacteria n.n. KBE/100ml
not detectable
0/100 ml Single value
Colony count 22 °C n.n. KBE/ml
not detectable
100 1/ml Single value
Colony count 36 °C n.n. KBE/ml
not detectable
20 1/ml Single value
Conductivity (25 °C) 491 µS/cm 2,500 µS/cm Single value
pH 7,29 - 6,5–9,5 Single value
Sodium 6,4 mg/l 200 mg/l
3 %
Single value
Sulphate 8,1 mg/l 250 mg/l
3 %
Single value

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (6)

Further parameters – GD Obertrum, TWA; Spielberggrabenquellen - PN Spielberggraben, Zulauf QSS oro re
Parameter Value Parametric value Share of the parametric value Reference
Acid capacity to pH 4.3 5,95 mmol/l Single value
Calcium 87 mg/l 400 mg/l
22 %
Single value
Hydrogen carbonate 363 mg/l Single value
Magnesium 19,0 mg/l 150 mg/l
13 %
Single value
Potassium 1,65 mg/l 50 mg/l
3 %
Single value
Total hardness 2,96 mmol/l Single value

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://www.obertrum.at/system/web/getDocument.ashx?cts=1777298777&fileid=2181805 · 14.04.2026 · Probenahme 31.03.2026 · retrieved on 14/08/2026

Postcodes in this zone: 5162

Frequently asked questions about drinking water in Nußdorf am Haunsberg, Obertrum am See, Seekirchen am Wallersee

How hard is the water in Nußdorf am Haunsberg, Obertrum am See, Seekirchen am Wallersee?
Marktgemeinde Obertrum am See publishes a total hardness of 2,96 mmol/l for the supply zone GD Obertrum, TWA; Spielberggrabenquellen - PN Spielberggraben, Zulauf QSS oro re — that corresponds to 16.6 °dH. The hardness range is a classification under the German Detergents and Cleaning Products Act (soft below 8,4 °dH, medium 8,4 to 14 °dH, hard above that) and not a quality verdict — it indicates how much calcium and magnesium is dissolved in the water. Basis: 14.04.2026, retrieved on 14/08/2026.
How much nitrate is in the drinking water in Nußdorf am Haunsberg, Obertrum am See, Seekirchen am Wallersee?
Marktgemeinde Obertrum am See publishes a nitrate value of 3,9 mg/l for the supply zone GD Obertrum, TWA; Spielberggrabenquellen - PN Spielberggraben, Zulauf QSS oro re. The statutory parametric value is 50 mg/l; the measured value represents 8 % of the parametric value. Basis: 14.04.2026, retrieved on 14/08/2026.
Who supplies the drinking water in Nußdorf am Haunsberg, Obertrum am See, Seekirchen am Wallersee?
Marktgemeinde Obertrum am See. The values shown here come from the supply zone GD Obertrum, TWA; Spielberggrabenquellen - PN Spielberggraben, Zulauf QSS oro re and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.

General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.