Skip to content
maunawai.info

Drinking water in Lauben

There are 2 places with this name — listed below by area. To determine the exact match, look up the postcode.

How to read the share of the parametric value

12 % Share of the parametric value. The proportion of the permitted maximum that the measured value uses — here 12 %, so just over an eighth.
< 10 % * Below the limit of quantification. The substance was not detectable. The mark shows where the detection limit lies relative to the parametric value — the actual share of the parametric value is below that.

Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.

Lauben (87761)

Brunnen I Lauben vor UV, an der äußeren Nachtweide 1, 87761 Lauben

Gemeinde Lauben-Frickenhausen

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

These values are more than a year old. The most recent analysis the water supplier has published for this zone dates from 26/11/2024. We have no newer values — which is why we show the latest available ones rather than none at all. They say nothing about how the water has changed since then.

Key values Brunnen I Lauben vor UV, an der äußeren Nachtweide 1, 87761 Lauben
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 31 mg/l 50 mg/l
62 %
Single value
Lead <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value
Sulphate 11 mg/l 250 mg/l
4 %
Single value
Sodium 9,0 mg/l 200 mg/l
5 %
Single value

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Show all recorded parameters (38 — most recent value per parameter)

Chemical parameters (21)

Chemical parameters – Brunnen I Lauben vor UV, an der äußeren Nachtweide 1, 87761 Lauben
Parameter Value Parametric value Share of the parametric value Reference
1,2-dichloroethane <0,0003 mg/l
below limit of quantification
3 µg/l
< 10 % *
Single value
Antimony <0,0003 mg/l
below limit of quantification
5 µg/l
< 6 % *
Single value
Arsenic 0,0002 mg/l 10 µg/l
2 %
Single value
Benzene <0,0003 mg/l
below limit of quantification
1 µg/l
< 30 % *
Single value
Benzo(a)pyrene <0,000003 mg/l
below limit of quantification
10 ng/l
< 30 % *
Single value
Bisphenol A <0,4 µg/l
below limit of quantification
2.5 µg/l
< 16 % *
Single value
Boron <0,1 mg/l
below limit of quantification
1 mg/l
< 10 % *
Single value
Bromate <0,002 mg/l
below limit of quantification
10 µg/l
< 20 % *
Single value
Cadmium <0,0001 mg/l
below limit of quantification
3 µg/l
< 3 % *
Single value
Chromium <0,0001 mg/l
below limit of quantification
25 µg/l
< 0.4 % *
Single value
Copper <0,003 mg/l
below limit of quantification
2 mg/l
< 0.2 % *
Single value
Fluoride <0,13 mg/l
below limit of quantification
1.5 mg/l
< 9 % *
Single value
Lead <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value
Mercury <0,0001 mg/l
below limit of quantification
1 µg/l
< 10 % *
Single value
Nickel <0,003 mg/l
below limit of quantification
20 µg/l
< 15 % *
Single value
Nitrate 31 mg/l 50 mg/l
62 %
Single value
Nitrite <0,03 mg/l
below limit of quantification
0.5 mg/l
< 6 % *
Single value
Polycyclic aromatic hydrocarbons <0,00003 mg/l
below limit of quantification
0.1 µg/l
< 30 % *
Single value
Selenium 0,005 mg/l 10 µg/l
50 %
Single value
Tetrachloroethene and Trichloroethene (sum) <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value
Uranium 0,0009 mg/l 10 µg/l
9 %
Single value

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Indicator parameters (13)

Indicator parameters – Brunnen I Lauben vor UV, an der äußeren Nachtweide 1, 87761 Lauben
Parameter Value Parametric value Share of the parametric value Reference
Aluminium <0,002 mg/l
below limit of quantification
0.2 mg/l
< 1 % *
Single value
Ammonium <0,04 mg/l
below limit of quantification
0.5 mg/l
< 8 % *
Single value
Chloride 13 mg/l 250 mg/l
5 %
Single value
Conductivity (25 °C) 648 µS/cm 2,790 µS/cm Single value
Iron <0,02 mg/l
below limit of quantification
0.2 mg/l
< 10 % *
Single value
Manganese <0,002 mg/l
below limit of quantification
50 µg/l
< 4 % *
Single value
Odour ohne Auffälligkeit - für den Verbraucher annehmbar Single value
pH 7,21 (14,6°C) - 6,5–9,5 Single value
Sodium 9,0 mg/l 200 mg/l
5 %
Single value
Sulphate 11 mg/l 250 mg/l
4 %
Single value
Taste nicht durchgeführt -
not determined
für den Verbraucher annehmbar Single value
Total organic carbon (TOC) 1,3 mg/l ohne anormale Veränderung Single value
Turbidity 0,15 NTU 1 NTU Single value

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (4)

Further parameters – Brunnen I Lauben vor UV, an der äußeren Nachtweide 1, 87761 Lauben
Parameter Value Parametric value Share of the parametric value Reference
Calcium 87,6 mg/l Single value
Magnesium 21,6 mg/l Single value
Phosphate <0,10 mg/l
below limit of quantification
Single value
Potassium 2,6 mg/l Single value

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://www.gemeinde-lauben.de/wp-content/uploads/2024/12/Wasserpruefberichte-Brunnen-Lauben.pdf · 26.11.2024 · Probenahme: 10.10.2024; Prüfzeitraum: 10.10.2024 bis 26.11.2024 · retrieved on 11/07/2026

Postcodes in this zone: 87761

Show 8 more supply zones

Rohwasser, Brunnen I Lauben vor UV, an der äußeren Nachtweide 1, 87761 Lauben

Gemeinde Lauben-Frickenhausen

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

These values are more than a year old. The most recent analysis the water supplier has published for this zone dates from 19/10/2024. We have no newer values — which is why we show the latest available ones rather than none at all. They say nothing about how the water has changed since then.

Key values Rohwasser, Brunnen I Lauben vor UV, an der äußeren Nachtweide 1, 87761 Lauben
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 31 mg/l 50 mg/l
62 %
Single value
Sulphate 11 mg/l 250 mg/l
4 %
Single value
Sodium 9,0 mg/l 200 mg/l
5 %
Single value
Show all recorded parameters (14 — most recent value per parameter)

Chemical parameters (1)

Chemical parameters – Rohwasser, Brunnen I Lauben vor UV, an der äußeren Nachtweide 1, 87761 Lauben
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 31 mg/l 50 mg/l
62 %
Single value

Indicator parameters (9)

Indicator parameters – Rohwasser, Brunnen I Lauben vor UV, an der äußeren Nachtweide 1, 87761 Lauben
Parameter Value Parametric value Share of the parametric value Reference
Chloride 13 mg/l 250 mg/l
5 %
Single value
Colour farblos - 0.5 m⁻¹ Single value
Conductivity (25 °C) 648 µS/cm 2,790 µS/cm Single value
Odour ohne Auffälligkeit - für den Verbraucher annehmbar Single value
pH 7,21 (14,6°C) - 6,5–9,5 Single value
Sodium 9,0 mg/l 200 mg/l
5 %
Single value
Sulphate 11 mg/l 250 mg/l
4 %
Single value
Temperature 14,6 °C Single value
Turbidity klar, kein Bodensatz (60 cm) - 1 NTU Single value

Further parameters (4)

Further parameters – Rohwasser, Brunnen I Lauben vor UV, an der äußeren Nachtweide 1, 87761 Lauben
Parameter Value Parametric value Share of the parametric value Reference
Calcium 87,6 mg/l Single value
Dissolved organic carbon (DOC) 1,0 mg/l Single value
Magnesium 21,6 mg/l Single value
Potassium 2,6 mg/l Single value

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://www.gemeinde-lauben.de/wp-content/uploads/2024/12/Wasserpruefberichte-Brunnen-Lauben.pdf · 26.11.2024 · Probenahme 10.10.2024 09:10 Uhr; Prüfzeitraum 10.10.2024 bis 19.10.2024 · retrieved on 11/07/2026

Postcodes in this zone: 87761

Trinkwasser (Probe-Nr. 2097456)

Gemeinde Lauben-Frickenhausen

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

These values are more than a year old. The most recent analysis the water supplier has published for this zone dates from 26/11/2024. We have no newer values — which is why we show the latest available ones rather than none at all. They say nothing about how the water has changed since then.

Key values Trinkwasser (Probe-Nr. 2097456)
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 31 mg/l 50 mg/l
62 %
Single value · Trinkwasser (Probe-Nr. 2097456)
Lead <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Sulphate 11 mg/l 250 mg/l
4 %
Single value · Trinkwasser (Probe-Nr. 2097456)
Sodium 9,0 mg/l 200 mg/l
5 %
Single value · Trinkwasser (Probe-Nr. 2097456)

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Show all recorded parameters (38 — most recent value per parameter)

Chemical parameters (21)

Chemical parameters – Trinkwasser (Probe-Nr. 2097456)
Parameter Value Parametric value Share of the parametric value Reference
1,2-dichloroethane <0,0003 mg/l
below limit of quantification
3 µg/l
< 10 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Antimony <0,0003 mg/l
below limit of quantification
5 µg/l
< 6 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Arsenic 0,0002 mg/l 10 µg/l
2 %
Single value · Trinkwasser (Probe-Nr. 2097456)
Benzene <0,0003 mg/l
below limit of quantification
1 µg/l
< 30 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Benzo(a)pyrene <0,000003 mg/l
below limit of quantification
10 ng/l
< 30 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Bisphenol A <0,4 µg/l
below limit of quantification
2.5 µg/l
< 16 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Boron <0,1 mg/l
below limit of quantification
1 mg/l
< 10 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Bromate <0,002 mg/l
below limit of quantification
10 µg/l
< 20 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Cadmium <0,0001 mg/l
below limit of quantification
3 µg/l
< 3 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Chromium <0,0001 mg/l
below limit of quantification
25 µg/l
< 0.4 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Copper <0,003 mg/l
below limit of quantification
2 mg/l
< 0.2 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Fluoride <0,13 mg/l
below limit of quantification
1.5 mg/l
< 9 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Lead <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Mercury <0,0001 mg/l
below limit of quantification
1 µg/l
< 10 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Nickel <0,003 mg/l
below limit of quantification
20 µg/l
< 15 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Nitrate 31 mg/l 50 mg/l
62 %
Single value · Trinkwasser (Probe-Nr. 2097456)
Nitrite <0,03 mg/l
below limit of quantification
0.5 mg/l
< 6 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Polycyclic aromatic hydrocarbons <0,00003 mg/l
below limit of quantification
0.1 µg/l
< 30 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Selenium 0,005 mg/l 10 µg/l
50 %
Single value · Trinkwasser (Probe-Nr. 2097456)
Tetrachloroethene and Trichloroethene (sum) <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Uranium 0,0009 mg/l 10 µg/l
9 %
Single value · Trinkwasser (Probe-Nr. 2097456)

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Indicator parameters (13)

Indicator parameters – Trinkwasser (Probe-Nr. 2097456)
Parameter Value Parametric value Share of the parametric value Reference
Aluminium <0,002 mg/l
below limit of quantification
0.2 mg/l
< 1 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Ammonium <0,04 mg/l
below limit of quantification
0.5 mg/l
< 8 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Chloride 13 mg/l 250 mg/l
5 %
Single value · Trinkwasser (Probe-Nr. 2097456)
Conductivity (25 °C) 648 µS/cm 2,790 µS/cm Single value · Trinkwasser (Probe-Nr. 2097456)
Iron <0,02 mg/l
below limit of quantification
0.2 mg/l
< 10 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Manganese <0,002 mg/l
below limit of quantification
50 µg/l
< 4 % *
Single value · Trinkwasser (Probe-Nr. 2097456)
Odour ohne Auffälligkeit - für den Verbraucher annehmbar Single value · Trinkwasser (Probe-Nr. 2097456)
pH 7,21 (14,6°C) - 6,5–9,5 Single value · Trinkwasser (Probe-Nr. 2097456)
Sodium 9,0 mg/l 200 mg/l
5 %
Single value · Trinkwasser (Probe-Nr. 2097456)
Sulphate 11 mg/l 250 mg/l
4 %
Single value · Trinkwasser (Probe-Nr. 2097456)
Taste nicht durchgeführt -
not determined
für den Verbraucher annehmbar Single value · Trinkwasser (Probe-Nr. 2097456)
Total organic carbon (TOC) 1,3 mg/l ohne anormale Veränderung Single value · Trinkwasser (Probe-Nr. 2097456)
Turbidity 0,15 NTU 1 NTU Single value · Trinkwasser (Probe-Nr. 2097456)

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (4)

Further parameters – Trinkwasser (Probe-Nr. 2097456)
Parameter Value Parametric value Share of the parametric value Reference
Calcium 87,6 mg/l Single value · Trinkwasser (Probe-Nr. 2097456)
Magnesium 21,6 mg/l Single value · Trinkwasser (Probe-Nr. 2097456)
Phosphate <0,10 mg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097456)
Potassium 2,6 mg/l Single value · Trinkwasser (Probe-Nr. 2097456)

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://www.gemeinde-lauben.de/wp-content/uploads/2024/12/Wasserpruefberichte-Brunnen-Lauben.pdf · 26.11.2024 · Probenahme 10.10.2024; Prüfzeiträume 10.10.2024 bis 26.11.2024 (versch. Teilberichte) · retrieved on 25/07/2026

Postcodes in this zone: 87761

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

These values are more than a year old. The most recent analysis the water supplier has published for this zone dates from 04/11/2024. We have no newer values — which is why we show the latest available ones rather than none at all. They say nothing about how the water has changed since then.

No core values are available for this zone yet.

Show all recorded parameters (48 — most recent value per parameter)

Chemical parameters (47)

Chemical parameters – lauben gesamt
Parameter Value Parametric value Share of the parametric value Reference
2,4-D <0,02 µg/l
below limit of quantification
Single value
Atrazine <0,02 µg/l
below limit of quantification
Single value
Azoxystrobin <0,02 µg/l
below limit of quantification
Single value
Bentazone <0,02 µg/l
below limit of quantification
Single value
Boscalid <0,02 µg/l
below limit of quantification
Single value
Bromacil <0,02 µg/l
below limit of quantification
Single value
Bromoxynil <0,02 µg/l
below limit of quantification
Single value
Carbendazim <0,02 µg/l
below limit of quantification
Single value
Carbetamide <0,02 µg/l
below limit of quantification
Single value
Chloridazon <0,02 µg/l
below limit of quantification
Single value
Chlorotoluron <0,02 µg/l
below limit of quantification
Single value
Clopyralid <0,05 µg/l
below limit of quantification
Single value
Desethylatrazine <0,02 µg/l
below limit of quantification
Single value
Dicamba <0,05 µg/l
below limit of quantification
Single value
Dichlorprop <0,02 µg/l
below limit of quantification
Single value
Diflufenican <0,02 µg/l
below limit of quantification
Single value
Dimefuron <0,02 µg/l
below limit of quantification
Single value
Dimethachlor <0,02 µg/l
below limit of quantification
Single value
Dimethenamid <0,02 µg/l
below limit of quantification
Single value
Dimethoate <0,02 µg/l
below limit of quantification
Single value
Diuron <0,02 µg/l
below limit of quantification
Single value
Ethidimuron <0,02 µg/l
below limit of quantification
Single value
Ethofumesate <0,02 µg/l
below limit of quantification
Single value
Flufenacet <0,02 µg/l
below limit of quantification
Single value
Glyphosate <0,05 µg/l
below limit of quantification
Single value
Imidacloprid <0,02 µg/l
below limit of quantification
Single value
Isoproturon <0,02 µg/l
below limit of quantification
Single value
Lenacil <0,02 µg/l
below limit of quantification
Single value
MCPA <0,02 µg/l
below limit of quantification
Single value
Mecoprop <0,02 µg/l
below limit of quantification
Single value
Metalaxyl <0,02 µg/l
below limit of quantification
Single value
Metamitron <0,02 µg/l
below limit of quantification
Single value
Metazachlor <0,02 µg/l
below limit of quantification
Single value
Metobromuron <0,02 µg/l
below limit of quantification
Single value
Metolachlor <0,02 µg/l
below limit of quantification
Single value
Metribuzin <0,02 µg/l
below limit of quantification
Single value
Nicosulfuron <0,02 µg/l
below limit of quantification
Single value
Pendimethalin <0,02 µg/l
below limit of quantification
Single value
Propazine <0,02 µg/l
below limit of quantification
Single value
Propiconazole <0,02 µg/l
below limit of quantification
Single value
Prosulfocarb <0,02 µg/l
below limit of quantification
Single value
Quinmerac <0,02 µg/l
below limit of quantification
Single value
Simazine <0,02 µg/l
below limit of quantification
Single value
Tebuconazole <0,02 µg/l
below limit of quantification
Single value
Terbuthylazine <0,02 µg/l
below limit of quantification
Single value
Thiacloprid <0,02 µg/l
below limit of quantification
Single value
Triadimenol <0,02 µg/l
below limit of quantification
Single value

Indicator parameters (1)

Indicator parameters – lauben gesamt
Parameter Value Parametric value Share of the parametric value Reference
Total organic carbon (TOC) 1,3 mg/l ohne anormale Veränderung Single value

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://www.gemeinde-lauben.de/wp-content/uploads/2024/12/Wasserpruefberichte-Brunnen-Lauben.pdf · 17.10.2024 - 04.11.2024 · retrieved on 11/07/2026

Postcodes in this zone: 87761

Trinkwasser (Probe-Nr. 2097455)

Gemeinde Lauben-Frickenhausen

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

These values are more than a year old. The most recent analysis the water supplier has published for this zone dates from 26/11/2024. We have no newer values — which is why we show the latest available ones rather than none at all. They say nothing about how the water has changed since then.

No core values are available for this zone yet.

Show all recorded parameters (5 — most recent value per parameter)

Indicator parameters (5)

Indicator parameters – Trinkwasser (Probe-Nr. 2097455)
Parameter Value Parametric value Share of the parametric value Reference
Conductivity (25 °C) 648 µS/cm 2,790 µS/cm Single value · Trinkwasser (Probe-Nr. 2097455)
Odour ohne Auffälligkeit - für den Verbraucher annehmbar Single value · Trinkwasser (Probe-Nr. 2097455)
pH 7,21 (14,6°C) - 6,5–9,5 Single value · Trinkwasser (Probe-Nr. 2097455)
Taste nicht durchgeführt -
not determined
für den Verbraucher annehmbar Single value · Trinkwasser (Probe-Nr. 2097455)
Turbidity 0,15 NTU 1 NTU Single value · Trinkwasser (Probe-Nr. 2097455)

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://www.gemeinde-lauben.de/wp-content/uploads/2024/12/Wasserpruefberichte-Brunnen-Lauben.pdf · 26.11.2024 · Probenahme 10.10.2024; Prüfzeiträume 10.10.2024 bis 26.11.2024 (versch. Teilberichte) · retrieved on 25/07/2026

Postcodes in this zone: 87761

Trinkwasser (Probe-Nr. 2097456) AGROLAB Fremduntersuchung

Gemeinde Lauben-Frickenhausen

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

These values are more than a year old. The most recent analysis the water supplier has published for this zone dates from 26/11/2024. We have no newer values — which is why we show the latest available ones rather than none at all. They say nothing about how the water has changed since then.

No core values are available for this zone yet.

Show all recorded parameters (1 — most recent value per parameter)

Indicator parameters (1)

Indicator parameters – Trinkwasser (Probe-Nr. 2097456) AGROLAB Fremduntersuchung
Parameter Value Parametric value Share of the parametric value Reference
Total organic carbon (TOC) 1,3 mg/l ohne anormale Veränderung Single value · Trinkwasser (Probe-Nr. 2097456) - AGROLAB Fremduntersuchung

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://www.gemeinde-lauben.de/wp-content/uploads/2024/12/Wasserpruefberichte-Brunnen-Lauben.pdf · 26.11.2024 · Probenahme 10.10.2024; Prüfzeiträume 10.10.2024 bis 26.11.2024 (versch. Teilberichte) · retrieved on 25/07/2026

Postcodes in this zone: 87761

Trinkwasser (Probe-Nr. 2097456) Rietzler Fremduntersuchung

Gemeinde Lauben-Frickenhausen

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

These values are more than a year old. The most recent analysis the water supplier has published for this zone dates from 26/11/2024. We have no newer values — which is why we show the latest available ones rather than none at all. They say nothing about how the water has changed since then.

No core values are available for this zone yet.

Show all recorded parameters (1 — most recent value per parameter)

Chemical parameters (1)

Chemical parameters – Trinkwasser (Probe-Nr. 2097456) Rietzler Fremduntersuchung
Parameter Value Parametric value Share of the parametric value Reference
Bisphenol A <0,4 µg/l
below limit of quantification
2.5 µg/l
< 16 % *
Single value · Trinkwasser (Probe-Nr. 2097456) - Rietzler Fremduntersuchung

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://www.gemeinde-lauben.de/wp-content/uploads/2024/12/Wasserpruefberichte-Brunnen-Lauben.pdf · 26.11.2024 · Probenahme 10.10.2024; Prüfzeiträume 10.10.2024 bis 26.11.2024 (versch. Teilberichte) · retrieved on 25/07/2026

Postcodes in this zone: 87761

Trinkwasser (Probe-Nr. 2097457)

Gemeinde Lauben-Frickenhausen

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

No core values are available for this zone yet.

Postcodes in this zone: 87761

Trinkwasser (Probe-Nr. 2097457) Rietzler PSM-Screening

Gemeinde Lauben-Frickenhausen

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

These values are more than a year old. The most recent analysis the water supplier has published for this zone dates from 26/11/2024. We have no newer values — which is why we show the latest available ones rather than none at all. They say nothing about how the water has changed since then.

No core values are available for this zone yet.

Show all recorded parameters (47 — most recent value per parameter)

Chemical parameters (47)

Chemical parameters – Trinkwasser (Probe-Nr. 2097457) Rietzler PSM-Screening
Parameter Value Parametric value Share of the parametric value Reference
2,4-D <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Atrazine <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Azoxystrobin <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Bentazone <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Boscalid <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Bromacil <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Bromoxynil <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Carbendazim <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Carbetamide <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Chloridazon <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Chlorotoluron <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Clopyralid <0,05 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Desethylatrazine <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Dicamba <0,05 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Dichlorprop <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Diflufenican <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Dimefuron <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Dimethachlor <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Dimethenamid <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Dimethoate <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Diuron <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Ethidimuron <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Ethofumesate <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Flufenacet <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Glyphosate <0,05 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Imidacloprid <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Isoproturon <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Lenacil <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
MCPA <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Mecoprop <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Metalaxyl <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Metamitron <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Metazachlor <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Metobromuron <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Metolachlor <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Metribuzin <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Nicosulfuron <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Pendimethalin <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Propazine <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Propiconazole <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Prosulfocarb <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Quinmerac <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Simazine <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Tebuconazole <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Terbuthylazine <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Thiacloprid <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening
Triadimenol <0,02 µg/l
below limit of quantification
Single value · Trinkwasser (Probe-Nr. 2097457) - Rietzler PSM-Screening

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://www.gemeinde-lauben.de/wp-content/uploads/2024/12/Wasserpruefberichte-Brunnen-Lauben.pdf · 26.11.2024 · Probenahme 10.10.2024; Prüfzeiträume 10.10.2024 bis 26.11.2024 (versch. Teilberichte) · retrieved on 25/07/2026

Postcodes in this zone: 87761

Frequently asked questions about drinking water in Lauben

How much nitrate is in the drinking water in Lauben?
Gemeinde Lauben-Frickenhausen publishes a nitrate value of 31 mg/l for the supply zone Brunnen I Lauben vor UV, an der äußeren Nachtweide 1, 87761 Lauben. The statutory parametric value is 50 mg/l; the measured value represents 62 % of the parametric value. Basis: 26.11.2024, retrieved on 11/07/2026.
Who supplies the drinking water in Lauben?
Gemeinde Lauben-Frickenhausen. The values shown here come from the supply zone Brunnen I Lauben vor UV, an der äußeren Nachtweide 1, 87761 Lauben and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.

General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.

No data yet

For postcode 87493 there is no verified assignment yet.