Skip to content
maunawai.info

Drinking water in Ihringen

One supply zone, water supplier: Gemeinde Ihringen am Kaiserstuhl.

How to read the share of the parametric value

12 % Share of the parametric value. The proportion of the permitted maximum that the measured value uses — here 12 %, so just over an eighth.
< 10 % * Below the limit of quantification. The substance was not detectable. The mark shows where the detection limit lies relative to the parametric value — the actual share of the parametric value is below that.

Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

No date is given for these values. The water supplier publishes the analysis without a sampling date and without a report date. When the water was examined is not apparent from the source — we do not add a date and we do not estimate one. What is stated is therefore only when we retrieved the document.

Key values Ihringen
Parameter Value Parametric value Share of the parametric value Reference
Sum of PFAS nb mg/l
not determined
0.1 µg/l Single value
Nitrate 33 mg/l 50 mg/l
66 %
Single value
Lead <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value
Escherichia coli (E. coli) 0 KBE/100 ml 0/100 ml Single value
Sulphate 31 mg/l 250 mg/l
12 %
Single value
Sodium 10,4 mg/l 200 mg/l
5 %
Single value

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Show all recorded parameters (66 — most recent value per parameter)

Microbiology (2)

Microbiology – Ihringen
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) 0 KBE/100 ml 0/100 ml Single value
Intestinal enterococci 0 KBE/100 ml 0/100 ml Single value

Chemical parameters (40)

Chemical parameters – Ihringen
Parameter Value Parametric value Share of the parametric value Reference
1,2-dichloroethane <0,0005 mg/l
below limit of quantification
3 µg/l
< 17 % *
Single value
2,6-Dichlorobenzamide (BAM) <0,00002 mg/l
below limit of quantification
Single value
Antimony <0,0012 mg/l
below limit of quantification
5 µg/l
< 24 % *
Single value
Arsenic <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value
Atrazine <0,00002 mg/l
below limit of quantification
Single value
Bentazone <0,00002 mg/l
below limit of quantification
Single value
Benzene <0,0002 mg/l
below limit of quantification
1 µg/l
< 20 % *
Single value
Benzo(a)pyrene <0,000003 mg/l
below limit of quantification
10 ng/l
< 30 % *
Single value
Benzo(b)fluoranthene <0,000020 mg/l
below limit of quantification
Single value
Benzo(k)fluoranthene <0,000020 mg/l
below limit of quantification
Single value
Bisphenol A <0,00075 mg/l
below limit of quantification
2.5 µg/l
< 30 % *
Single value
Boron <0,1 mg/l
below limit of quantification
1 mg/l
< 10 % *
Single value
Bromacil <0,00002 mg/l
below limit of quantification
Single value
Bromate <0,003 mg/l
below limit of quantification
10 µg/l
< 30 % *
Single value
Cadmium <0,0003 mg/l
below limit of quantification
3 µg/l
< 10 % *
Single value
Chromium 0,00054 mg/l 25 µg/l
2 %
Single value
Copper <0,1 mg/l
below limit of quantification
2 mg/l
< 5 % *
Single value
Cyanide <0,005 mg/l
below limit of quantification
50 µg/l
< 10 % *
Single value
Desethylatrazine <0,00002 mg/l
below limit of quantification
Single value
Desethylterbuthylazine <0,00002 mg/l
below limit of quantification
Single value
Desisopropylatrazine <0,00002 mg/l
below limit of quantification
Single value
Fluoride <0,10 mg/l
below limit of quantification
1.5 mg/l
< 7 % *
Single value
Hexazinone <0,00002 mg/l
below limit of quantification
Single value
Indeno(1,2,3-cd)pyrene <0,000020 mg/l
below limit of quantification
Single value
Lead <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value
Mercury <0,0001 mg/l
below limit of quantification
1 µg/l
< 10 % *
Single value
Metalaxyl <0,00002 mg/l
below limit of quantification
Single value
Metazachlor <0,00002 mg/l
below limit of quantification
Single value
Metolachlor <0,00002 mg/l
below limit of quantification
Single value
Nickel <0,002 mg/l
below limit of quantification
20 µg/l
< 10 % *
Single value
Nitrate 33 mg/l 50 mg/l
66 %
Single value
Nitrite <0,01 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Single value
Propazine <0,00002 mg/l
below limit of quantification
Single value
Selenium <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Single value
Simazine <0,00002 mg/l
below limit of quantification
Single value
Terbuthylazine <0,00002 mg/l
below limit of quantification
Single value
Tetrachloroethene <0,0005 mg/l
below limit of quantification
Single value
Tetrachloroethene and Trichloroethene (sum) nb mg/l
not determined
10 µg/l Single value
Trichloroethene <0,0005 mg/l
below limit of quantification
Single value
Uranium 0,002 mg/l 10 µg/l
20 %
Single value

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

PFAS (2)

PFAS – Ihringen
Parameter Value Parametric value Share of the parametric value Reference
Sum of 4 PFAS nb mg/l
not determined
Single value
Sum of PFAS nb mg/l
not determined
0.1 µg/l Single value

Indicator parameters (17)

Indicator parameters – Ihringen
Parameter Value Parametric value Share of the parametric value Reference
Aluminium <0,020 mg/l
below limit of quantification
0.2 mg/l
< 10 % *
Single value
Ammonium <0,01 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Single value
Chloride 25 mg/l 250 mg/l
10 %
Single value
Coliform bacteria 0 KBE/100 ml 0/100 ml Single value
Colony count 22 °C 0 KBE/ml ohne anormale Veränderung Single value
Colony count 36 °C 0 KBE/ml ohne anormale Veränderung Single value
Colour <0,05 1/m
below limit of quantification
0.5 m⁻¹ Single value
Conductivity (25 °C) 614 µS/cm 2,790 µS/cm Single value
Iron 0,046 mg/l 0.2 mg/l
23 %
Single value
Manganese <0,005 mg/l
below limit of quantification
50 µg/l
< 10 % *
Single value
Odour ohne - für den Verbraucher annehmbar Single value
pH 7,53 - 6,5–9,5 Single value
Sodium 10,4 mg/l 200 mg/l
5 %
Single value
Sulphate 31 mg/l 250 mg/l
12 %
Single value
Temperature 10,3 °C Single value
Total organic carbon (TOC) 0,46 mg/l ohne anormale Veränderung Single value
Turbidity 0,70 NTU 1 NTU Single value

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (5)

Further parameters – Ihringen
Parameter Value Parametric value Share of the parametric value Reference
Acid capacity to pH 4.3 4,42 mmol/l Single value
Base capacity to pH 8.2 0,48 mmol/l Single value
Calcium 106,0 mg/l Single value
Magnesium 11,7 mg/l Single value
Potassium 1,6 mg/l Single value

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Postcodes in this zone: 79241

Frequently asked questions about drinking water in Ihringen

How much nitrate is in the drinking water in Ihringen?
Gemeinde Ihringen am Kaiserstuhl publishes a nitrate value of 33 mg/l for the supply zone Ihringen. The statutory parametric value is 50 mg/l; the measured value represents 66 % of the parametric value. Basis: Publication by the water supplier, retrieved on 27/07/2026.
Who supplies the drinking water in Ihringen?
Gemeinde Ihringen am Kaiserstuhl. The values shown here come from the supply zone Ihringen and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.

General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.