Drinking water in Hürth
One supply zone, water supplier: SWH (Stadtwerke Hürth).
How to read the share of the parametric value
Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.
Werksausgang, Wasserwerk Hürth-Efferen
SWH (Stadtwerke Hürth)Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.
These values are more than a year old. The most recent analysis the water supplier has published for this zone dates from 03/04/2025. We have no newer values — which is why we show the latest available ones rather than none at all. They say nothing about how the water has changed since then.
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Nitrate | <5,0 mg/l below limit of quantification | 50 mg/l | < 10 % * | Single value |
| Lead | <0,0005 mg/l below limit of quantification | 10 µg/l | < 5 % * | Single value |
| Sulphate | 27,8 mg/l | 250 mg/l | 11 % | Single value |
| Sodium | 56,4 mg/l | 200 mg/l | 28 % | Single value |
* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.
Show all recorded parameters (41 — most recent value per parameter)
Chemical parameters (19)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| 1,2-dichloroethane | <0,0002 mg/l below limit of quantification | 3 µg/l | < 7 % * | Single value |
| Antimony | <0,0005 mg/l below limit of quantification | 5 µg/l | < 10 % * | Single value |
| Arsenic | <0,0005 mg/l below limit of quantification | 10 µg/l | < 5 % * | Single value |
| Boron | 0,1 mg/l | 1 mg/l | 10 % | Single value |
| Cadmium | <0,0001 mg/l below limit of quantification | 3 µg/l | < 3 % * | Single value |
| Chromium | <0,0005 mg/l below limit of quantification | 25 µg/l | < 2 % * | Single value |
| Copper | <0,02 mg/l below limit of quantification | 2 mg/l | < 1 % * | Single value |
| Fluoride | 0,44 mg/l | 1.5 mg/l | 29 % | Single value |
| Lead | <0,0005 mg/l below limit of quantification | 10 µg/l | < 5 % * | Single value |
| Mercury | <0,0001 mg/l below limit of quantification | 1 µg/l | < 10 % * | Single value |
| Nickel | <0,0010 mg/l below limit of quantification | 20 µg/l | < 5 % * | Single value |
| Nitrate | <5,0 mg/l below limit of quantification | 50 mg/l | < 10 % * | Single value |
| Nitrite | <0,01 mg/l below limit of quantification | 0.5 mg/l | < 2 % * | Single value |
| Pesticides — Total | <0,0005 mg/l below limit of quantification | 0.5 µg/l | < 100 % * | Single value |
| Polycyclic aromatic hydrocarbons | 0 mg/l | 0.1 µg/l | 0 % | Single value |
| Selenium | <0,0005 mg/l below limit of quantification | 10 µg/l | < 5 % * | Single value |
| Tetrachloroethene and Trichloroethene (sum) | 0 mg/l | 10 µg/l | 0 % | Single value |
| Trihalomethanes — Total | 0 mg/l | 50 µg/l | 0 % | Single value |
| Uranium | <0,0001 mg/l below limit of quantification | 10 µg/l | < 1 % * | Single value |
* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.
Indicator parameters (14)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Aluminium | <0,04 mg/l below limit of quantification | 0.2 mg/l | < 20 % * | Single value |
| Ammonium | <0,05 mg/l below limit of quantification | 0.5 mg/l | < 10 % * | Single value |
| Calcite dissolution capacity | -6,23 mg/l | 5 mg/l CaCO3 | — | Single value |
| Chloride | 47,7 mg/l | 250 mg/l | 19 % | Single value |
| Colony count 36 °C | 0 /ml | ohne anormale Veränderung | — | Single value |
| Colour | 0,31 m-1 | 0.5 m⁻¹ | — | Single value |
| Conductivity (25 °C) | 544 µS/cm | 2,790 µS/cm | — | Single value |
| Manganese | <0,001 mg/l below limit of quantification | 50 µg/l | < 2 % * | Single value |
| pH | 7,64 | 6,5–9,5 | — | Single value |
| Sodium | 56,4 mg/l | 200 mg/l | 28 % | Single value |
| Sulphate | 27,8 mg/l | 250 mg/l | 11 % | Single value |
| Temperature | 13,0 °C | — | — | Single value |
| Total organic carbon (TOC) | 3,0 mg/l | ohne anormale Veränderung | — | Single value |
| Turbidity | 0,08 NTU | 1 NTU | — | Single value |
* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.
Further parameters (8)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Acid capacity to pH 4.3 | 4,21 mol/m3 | — | — | Single value |
| Base capacity to pH 8.2 | 0,20 mol/m3 | — | — | Single value |
| Calcium | 50,2 mg/l | — | — | Single value |
| Carbonate hardness | 10,1 °dH | — | — | Single value |
| Magnesium | 13,6 mg/l | — | — | Single value |
| Phosphate | bis zu 2,0 mg/l | — | — | Single value |
| Potassium | 5,6 mg/l | — | — | Single value |
| Sum of alkaline earth metals | 1,81 mmol/l | — | — | Single value |
Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.
Postcodes in this zone: 50354
Frequently asked questions about drinking water in Hürth
- How much nitrate is in the drinking water in Hürth?
- SWH (Stadtwerke Hürth) publishes a nitrate value of <5,0 mg/l for the supply zone Werksausgang, Wasserwerk Hürth-Efferen. The statutory parametric value is 50 mg/l; the measured value lies below it and cannot be specified more precisely below the limit of quantification. Basis: Publication by the water supplier, retrieved on 11/07/2026.
- Who supplies the drinking water in Hürth?
- SWH (Stadtwerke Hürth). The values shown here come from the supply zone Werksausgang, Wasserwerk Hürth-Efferen and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.
General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.