Drinking water in Enzenkirchen, Kopfing im Innkreis, St. Aegidi
One supply zone, water supplier: Marktgemeinde Kopfing.
How to read the share of the parametric value
Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.
WV Marktgemeinde Kopfing, Entnahmestelle 03: Zulauf HB nach Aufbereitung
Marktgemeinde KopfingAssigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Nitrate | 19,8 mg/l | 50 mg/l | 40 % | Single value |
| Escherichia coli (E. coli) | 0 KBE/100ml | 0/100 ml | — | Single value |
| Sulphate | 4,5 mg/l | 250 mg/l | 2 % | Single value |
| Sodium | 6,13 mg/l | 200 mg/l | 3 % | Single value |
Show all recorded parameters (32 — most recent value per parameter)
Microbiology (3)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Escherichia coli (E. coli) | 0 KBE/100ml | 0/100 ml | — | Single value |
| Intestinal enterococci | 0 KBE/100ml | 0/100 ml | — | Single value |
| Pseudomonas aeruginosa | 0 KBE/100ml | 0/100 ml | — | Single value |
Chemical parameters (3)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Nitrate | 19,8 mg/l | 50 mg/l | 40 % | Single value |
| Nitrate/50 + Nitrite/3 | 0,399 mg/l | — | — | Single value |
| Nitrite | <0,01 mg/l below limit of quantification | 0.1 mg/l | < 10 % * | Single value |
* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.
Indicator parameters (17)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Ammonium | 0,019 mg/l | 0.5 mg/l | 4 % | Single value |
| Calcite dissolution capacity | 2,22 mg/l | — | — | Single value |
| Chloride | 10,9 mg/l | 200 mg/l | 5 % | Single value |
| Coliform bacteria | 0 KBE/100ml | 0/100 ml | — | Single value |
| Colony count 22 °C | 5 KBE/ml | 100 1/ml | — | Single value |
| Colony count 36 °C | 0 KBE/ml | 20 1/ml | — | Single value |
| Colour | farblos, klar, ohne Bodensatz | — | — | Single value |
| Conductivity (25 °C) | 216 µS/cm | 2,500 µS/cm | — | Single value |
| Iron | <0,01 mg/l below limit of quantification | 0.2 mg/l | < 5 % * | Single value |
| Manganese | <0,005 mg/l below limit of quantification | 50 µg/l | < 10 % * | Single value |
| Odour | geruchlos | — | — | Single value |
| Oxidisability | <0,10 (NWG) mg O2/l not detectable | 5 mg/l | — | Single value |
| pH | 7,92 | 6,5–9,5 | — | Single value |
| Sodium | 6,13 mg/l | 200 mg/l | 3 % | Single value |
| Sulphate | 4,5 mg/l | 250 mg/l | 2 % | Single value |
| Taste | geschmacklos | — | — | Single value |
| Temperature | 9,2 °C | — | — | Single value |
* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.
Further parameters (9)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Acid capacity to pH 4.3 | 1,70 mmol/l | — | — | Single value |
| Base capacity to pH 8.2 | 0,03 mmol/l | — | — | Single value |
| Calcium | 31,4 mg/l | 400 mg/l | 8 % | Single value |
| Carbonate hardness | 4,62 °dH | — | — | Single value |
| Hydrogen carbonate | 101 mg/l | — | — | Single value |
| Magnesium | 5,67 mg/l | 150 mg/l | 4 % | Single value |
| Potassium | 1,26 mg/l | 50 mg/l | 3 % | Single value |
| Saturation index | -0,21 | — | — | Single value |
| Total hardness | 1,02 mmol/l | — | — | Single value |
Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.
Postcodes in this zone: 4794
Frequently asked questions about drinking water in Enzenkirchen, Kopfing im Innkreis, St. Aegidi
- How hard is the water in Enzenkirchen, Kopfing im Innkreis, St. Aegidi?
- Marktgemeinde Kopfing publishes a total hardness of 1,02 mmol/l for the supply zone WV Marktgemeinde Kopfing, Entnahmestelle 03: Zulauf HB nach Aufbereitung — that corresponds to 5.7 °dH. The hardness range is a classification under the German Detergents and Cleaning Products Act (soft below 8,4 °dH, medium 8,4 to 14 °dH, hard above that) and not a quality verdict — it indicates how much calcium and magnesium is dissolved in the water. Basis: 27.05.2026, retrieved on 26/08/2026.
- How much nitrate is in the drinking water in Enzenkirchen, Kopfing im Innkreis, St. Aegidi?
- Marktgemeinde Kopfing publishes a nitrate value of 19,8 mg/l for the supply zone WV Marktgemeinde Kopfing, Entnahmestelle 03: Zulauf HB nach Aufbereitung. The statutory parametric value is 50 mg/l; the measured value represents 40 % of the parametric value. Basis: 27.05.2026, retrieved on 26/08/2026.
- Who supplies the drinking water in Enzenkirchen, Kopfing im Innkreis, St. Aegidi?
- Marktgemeinde Kopfing. The values shown here come from the supply zone WV Marktgemeinde Kopfing, Entnahmestelle 03: Zulauf HB nach Aufbereitung and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.
General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.