Skip to content
maunawai.info

Drinking water in Barby

2 supply zones — values can differ depending on the district. Below is the zone with the most documented parameters, the others collapsed underneath. To determine the exact match, look up the postcode.

How to read the share of the parametric value

12 % Share of the parametric value. The proportion of the permitted maximum that the measured value uses — here 12 %, so just over an eighth.
< 10 % * Below the limit of quantification. The substance was not detectable. The mark shows where the detection limit lies relative to the parametric value — the actual share of the parametric value is below that.

Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.

Versorgungsbereich Wasserwerk Colbitz

TWM GmbH - Trinkwasserversorgung Magdeburg GmbH

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

Water hardness
14.3 °dH
Hardness range hart
Key values Versorgungsbereich Wasserwerk Colbitz
Parameter Value Parametric value Share of the parametric value Reference
Nitrate <1,0 mg/l
below limit of quantification
50 mg/l
< 2 % *
Mean
Lead <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Escherichia coli (E. coli) 0 KBE/100 ml 0/100 ml Mean
Sulphate 110 mg/l 250 mg/l
44 %
Mean
Sodium 0,985 mmol/l 200 mg/l Mean

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Show all recorded parameters (92 — most recent value per parameter)

Microbiology (2)

Microbiology – Versorgungsbereich Wasserwerk Colbitz
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) 0 KBE/100 ml 0/100 ml Mean
Intestinal enterococci 0 KBE/100 ml 0/100 ml Mean

Chemical parameters (60)

Chemical parameters – Versorgungsbereich Wasserwerk Colbitz
Parameter Value Parametric value Share of the parametric value Reference
1,2-dichloroethane <0,00050 mg/l
below limit of quantification
3 µg/l
< 17 % *
Mean
Antimony <0,0010 mg/l
below limit of quantification
5 µg/l
< 20 % *
Mean
Arsenic <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Atrazine <0,000030 mg/l
below limit of quantification
Mean
Azoxystrobin <0,000030 mg/l
below limit of quantification
Mean
Bentazone <0,000030 mg/l
below limit of quantification
Mean
Benzene <0,00030 mg/l
below limit of quantification
1 µg/l
< 30 % *
Mean
Benzo(a)pyrene <0,0000025 mg/l
below limit of quantification
10 ng/l
< 25 % *
Mean
Benzo(b)fluoranthene <0,000025 mg/l
below limit of quantification
Mean
Benzo(ghi)perylene <0,000025 mg/l
below limit of quantification
Mean
Benzo(k)fluoranthene <0,000025 mg/l
below limit of quantification
Mean
Bisphenol A <0,00018 mg/l
below limit of quantification
2.5 µg/l
< 7 % *
Mean
Boron <0,100 mg/l
below limit of quantification
1 mg/l
< 10 % *
Mean
Bromacil <0,000030 mg/l
below limit of quantification
Mean
Bromate <0,002 mg/l
below limit of quantification
10 µg/l
< 20 % *
Mean
Bromoxynil <0,000030 mg/l
below limit of quantification
Mean
Cadmium <0,0003 mg/l
below limit of quantification
3 µg/l
< 10 % *
Mean
Chloridazon <0,000030 mg/l
below limit of quantification
Mean
Chlorotoluron <0,000030 mg/l
below limit of quantification
Mean
Chromium <0,000068 mg/l
below limit of quantification
25 µg/l
< 0.3 % *
Mean
Copper <0,0020 mg/l
below limit of quantification
2 mg/l
< 0.1 % *
Mean
Cyanide <0,010 mg/l
below limit of quantification
50 µg/l
< 20 % *
Mean
Dichlorprop <0,000030 mg/l
below limit of quantification
Mean
Dimefuron <0,000030 mg/l
below limit of quantification
Mean
Dimethachlor <0,000030 mg/l
below limit of quantification
Mean
Dimethenamid <0,000030 mg/l
below limit of quantification
Mean
Dimethoate <0,000030 mg/l
below limit of quantification
Mean
Diuron <0,000030 mg/l
below limit of quantification
Mean
Ethidimuron <0,000030 mg/l
below limit of quantification
Mean
Fluoride <0,20 mg/l
below limit of quantification
1.5 mg/l
< 13 % *
Mean
Hexazinone <0,000030 mg/l
below limit of quantification
Mean
Indeno(1,2,3-cd)pyrene <0,000025 mg/l
below limit of quantification
Mean
Isoproturon <0,000030 mg/l
below limit of quantification
Mean
Lead <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Lenacil <0,000030 mg/l
below limit of quantification
Mean
MCPA <0,000030 mg/l
below limit of quantification
Mean
Mecoprop <0,000030 mg/l
below limit of quantification
Mean
Mercury <0,0001 mg/l
below limit of quantification
1 µg/l
< 10 % *
Mean
Metamitron <0,000030 mg/l
below limit of quantification
Mean
Metazachlor 0,000208 mg/l Mean
Methabenzthiazuron <0,000030 mg/l
below limit of quantification
Mean
Metolachlor 0,000062 mg/l Mean
Metoxuron <0,000030 mg/l
below limit of quantification
Mean
Metribuzin <0,000030 mg/l
below limit of quantification
Mean
Nickel <0,0020 mg/l
below limit of quantification
20 µg/l
< 10 % *
Mean
Nitrate <1,0 mg/l
below limit of quantification
50 mg/l
< 2 % *
Mean
Nitrite <0,010 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Mean
Prometryn <0,000030 mg/l
below limit of quantification
Mean
Propazine <0,000030 mg/l
below limit of quantification
Mean
Quinmerac <0,000030 mg/l
below limit of quantification
Mean
Sebuthylazine <0,000030 mg/l
below limit of quantification
Mean
Selenium <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Simazine <0,000030 mg/l
below limit of quantification
Mean
Tebuconazole <0,000030 mg/l
below limit of quantification
Mean
Terbuthylazine <0,000030 mg/l
below limit of quantification
Mean
Tetrachloroethene <0,0010 mg/l
below limit of quantification
Mean
Thiacloprid <0,000030 mg/l
below limit of quantification
Mean
Trichloroethene <0,0010 mg/l
below limit of quantification
Mean
Uranium <0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Vinyl chloride <0,00015 mg/l
below limit of quantification
0.5 µg/l
< 30 % *
Mean

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Metabolites (2)

Metabolites – Versorgungsbereich Wasserwerk Colbitz
Parameter Value Parametric value Share of the parametric value Reference
Desphenyl-chloridazon <0,000038 mg/l
below limit of quantification
Mean
Methyl-desphenyl-chloridazon <0,000030 mg/l
below limit of quantification
Mean

Indicator parameters (20)

Indicator parameters – Versorgungsbereich Wasserwerk Colbitz
Parameter Value Parametric value Share of the parametric value Reference
Aluminium <0,020 mg/l
below limit of quantification
0.2 mg/l
< 10 % *
Mean
Ammonium <0,01 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Mean
Calcite dissolution capacity -2 mg/l 5 mg/l CaCO3 Mean
Chloride 41 mg/l 250 mg/l
16 %
Mean
Coliform bacteria 0 KBE/100 ml 0/100 ml Mean
Colony count 22 °C 0 KBE/ml ohne anormale Veränderung Mean
Colony count 36 °C 0 KBE/ml ohne anormale Veränderung Mean
Colour ohne ohne 0.5 m⁻¹ Mean
Conductivity (25 °C) 601 µS/cm 2,790 µS/cm Mean
Iron <0,013 mg/l
below limit of quantification
0.2 mg/l
< 6 % *
Mean
Manganese <0,002 mg/l
below limit of quantification
50 µg/l
< 4 % *
Mean
Odour ohne ohne für den Verbraucher annehmbar Mean
Oxidisability 2,8 mg/l O2 5 mg/l O2 Mean
pH 7,61 ohne 6,5–9,5 Mean
Sodium 0,985 mmol/l 200 mg/l Mean
Sulphate 110 mg/l 250 mg/l
44 %
Mean
Taste ohne ohne für den Verbraucher annehmbar Mean
Temperature 20,3 °C Mean
Total organic carbon (TOC) 4,32 mg/l C ohne anormale Veränderung Mean
Turbidity 0,24 NTU 1 NTU Mean

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (8)

Further parameters – Versorgungsbereich Wasserwerk Colbitz
Parameter Value Parametric value Share of the parametric value Reference
Calcium 2,28 mmol/l Mean
Hardness range (WRMG) hart ohne Mean
Magnesium 0,27 mmol/l Mean
Oxygen 9,8 mg/l O2 Mean
Potassium 0,091 mmol/l Mean
Saturation index 0,07 ohne Mean
Silicate / silicic acid 13,13 mg/l Mean
Total hardness 14,3 °dH Mean

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://www.wasser-twm.de/media/uploads/wasserqualitaeten/2025/WW-Colbitz-2025.pdf · 26.01.2026 · Jahresmittelwert 2025 · retrieved on 25/07/2026

Postcodes in this zone: 39249

Show 1 more supply zone

WVG MW Colbitz/Lindau

WVG MW Colbitz/Lindau

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

These values are more than a year old. The most recent analysis the water supplier has published for this zone dates from 31/12/2023. We have no newer values — which is why we show the latest available ones rather than none at all. They say nothing about how the water has changed since then.

Key values WVG MW Colbitz/Lindau
Parameter Value Parametric value Share of the parametric value Reference
Sulphate 84,2755 mg/l 250 mg/l
34 %
Mean · WVG MW Colbitz/Lindau
Sodium 14,31 mg/l 200 mg/l
7 %
Mean · WVG MW Colbitz/Lindau
Show all recorded parameters (12 — most recent value per parameter)

Chemical parameters (6)

Chemical parameters – WVG MW Colbitz/Lindau
Parameter Value Parametric value Share of the parametric value Reference
Boron 0,02 mg/l 1 mg/l
2 %
Mean · WVG MW Colbitz/Lindau
Chromium 0,0002 mg/l 25 µg/l
0.8 %
Mean · WVG MW Colbitz/Lindau
Copper 0,0127 mg/l 2 mg/l
0.6 %
Mean · WVG MW Colbitz/Lindau
Fluoride 0,16 mg/l 1.5 mg/l
11 %
Mean · WVG MW Colbitz/Lindau
Nitrite 0,01 mg/l 0.5 mg/l
2 %
Mean · WVG MW Colbitz/Lindau
Selenium 0,002 mg/l 10 µg/l
20 %
Mean · WVG MW Colbitz/Lindau

Indicator parameters (6)

Indicator parameters – WVG MW Colbitz/Lindau
Parameter Value Parametric value Share of the parametric value Reference
Aluminium 0,027 mg/l 0.2 mg/l
13 %
Mean · WVG MW Colbitz/Lindau
Ammonium 0,01 mg/l 0.5 mg/l
2 %
Mean · WVG MW Colbitz/Lindau
Chloride 24,613889 mg/l 250 mg/l
10 %
Mean · WVG MW Colbitz/Lindau
Iron 0,029 mg/l 0.2 mg/l
15 %
Mean · WVG MW Colbitz/Lindau
Sodium 14,31 mg/l 200 mg/l
7 %
Mean · WVG MW Colbitz/Lindau
Sulphate 84,2755 mg/l 250 mg/l
34 %
Mean · WVG MW Colbitz/Lindau

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://lavst.azurewebsites.net/wasserkarte/gemeinden/15082256b.pdf · Jahresmittel 2023 · Jahresmittel 2023 · retrieved on 18/08/2026

Postcodes in this zone: 39249

Frequently asked questions about drinking water in Barby

How hard is the water in Barby?
TWM GmbH - Trinkwasserversorgung Magdeburg GmbH publishes a total hardness of 14.3 °dH for the supply zone Versorgungsbereich Wasserwerk Colbitz (hardness range hart). The hardness range is a classification under the German Detergents and Cleaning Products Act (soft below 8,4 °dH, medium 8,4 to 14 °dH, hard above that) and not a quality verdict — it indicates how much calcium and magnesium is dissolved in the water. Basis: 26.01.2026, retrieved on 25/07/2026.
How much nitrate is in the drinking water in Barby?
TWM GmbH - Trinkwasserversorgung Magdeburg GmbH publishes a nitrate value of <1,0 mg/l for the supply zone Versorgungsbereich Wasserwerk Colbitz. The statutory parametric value is 50 mg/l; the measured value lies below it and cannot be specified more precisely below the limit of quantification. Basis: 26.01.2026, retrieved on 25/07/2026.
Who supplies the drinking water in Barby?
TWM GmbH - Trinkwasserversorgung Magdeburg GmbH. The values shown here come from the supply zone Versorgungsbereich Wasserwerk Colbitz and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.

General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.