Skip to content
maunawai.info

Drinking water in 76199

For this postcode Stadtwerke Karlsruhe publishes several supply zones. Which of them serves an individual address is not published — below are the values of the zone with the most documented parameters, the remaining 1 underneath.

How to read the share of the parametric value

12 % Share of the parametric value. The proportion of the permitted maximum that the measured value uses — here 12 %, so just over an eighth.
< 10 % * Below the limit of quantification. The substance was not detectable. The mark shows where the detection limit lies relative to the parametric value — the actual share of the parametric value is below that.

Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.

Karlsruher Höhenstadtteile (Wasserbezug vom Zweckverband für die Wasserversorgung des Hügellandes zwischen Alb und Pfinz)

Stadtwerke Karlsruhe

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

Water hardness
18.6 °dH
Hardness range hart
Key values Karlsruher Höhenstadtteile (Wasserbezug vom Zweckverband für die Wasserversorgung des Hügellandes zwischen Alb und Pfinz)
Parameter Value Parametric value Share of the parametric value Reference
Sum of PFAS n.b. mg/l
not determined
Mean
Nitrate 10,3 mg/l 50 mg/l
21 %
Mean
Lead < 0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Escherichia coli (E. coli) 0 Anz./100 ml 0/100 ml Mean
Sulphate 29,9 mg/l 250 mg/l
12 %
Mean
Sodium 7,4 mg/l 200 mg/l
4 %
Mean

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Show all recorded parameters (73 — most recent value per parameter)

Microbiology (2)

Microbiology – Karlsruher Höhenstadtteile (Wasserbezug vom Zweckverband für die Wasserversorgung des Hügellandes zwischen Alb und Pfinz)
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) 0 Anz./100 ml 0/100 ml Mean
Intestinal enterococci 0 Anz./100 ml 0/100 ml Mean

Chemical parameters (32)

Chemical parameters – Karlsruher Höhenstadtteile (Wasserbezug vom Zweckverband für die Wasserversorgung des Hügellandes zwischen Alb und Pfinz)
Parameter Value Parametric value Share of the parametric value Reference
1,2-dichloroethane < 0,0001 mg/l
below limit of quantification
3 µg/l
< 3 % *
Mean
Acrylamide n.a. mg/l
not detectable
0.1 µg/l Mean
Antimony < 0,001 mg/l
below limit of quantification
5 µg/l
< 20 % *
Mean
Arsenic 0,001 mg/l 10 µg/l
10 %
Mean
Benzene < 0,0001 mg/l
below limit of quantification
1 µg/l
< 10 % *
Mean
Benzo(a)pyrene < 0,000002 mg/l
below limit of quantification
10 ng/l
< 20 % *
Mean
Bisphenol A < 0,000005 mg/l
below limit of quantification
2.5 µg/l
< 0.2 % *
Mean
Boron < 0,02 mg/l
below limit of quantification
1 mg/l
< 2 % *
Mean
Bromate 0,001 mg/l 10 µg/l
10 %
Mean
Cadmium < 0,0001 mg/l
below limit of quantification
3 µg/l
< 3 % *
Mean
Chlorate n.a. mg/l
not detectable
70 µg/l Mean
Chlorite n.a. mg/l
not detectable
0.2 mg/l Mean
Chromium < 0,0005 mg/l
below limit of quantification
25 µg/l
< 2 % *
Mean
Copper 0,01 mg/l 2 mg/l
0.5 %
Mean
Cyanide < 0,01 mg/l
below limit of quantification
50 µg/l
< 20 % *
Mean
Epichlorohydrin n.a. mg/l
not detectable
0.1 µg/l Mean
Fluoride 0,08 mg/l 1.5 mg/l
5 %
Mean
Haloacetic acids (HAA) n.a. mg/l
not detectable
Mean
Lead < 0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Mercury < 0,00005 mg/l
below limit of quantification
1 µg/l
< 5 % *
Mean
Microcystin-LR n.a. mg/l
not detectable
Mean
Nickel < 0,001 mg/l
below limit of quantification
20 µg/l
< 5 % *
Mean
Nitrate 10,3 mg/l 50 mg/l
21 %
Mean
Nitrite < 0,01 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Mean
Pesticides n.b. mg/l
not determined
0.1 µg/l Mean
Pesticides — Total n.b. mg/l
not determined
0.5 µg/l Mean
Polycyclic aromatic hydrocarbons n.b. mg/l
not determined
0.1 µg/l Mean
Selenium < 0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Tetrachloroethene and Trichloroethene (sum) 0,0007 mg/l 10 µg/l
7 %
Mean
Trihalomethanes — Total 0,0009 mg/l 50 µg/l
2 %
Mean
Uranium 0,0012 mg/l 10 µg/l
12 %
Mean
Vinyl chloride n.a. mg/l
not detectable
0.5 µg/l Mean

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

PFAS (2)

PFAS – Karlsruher Höhenstadtteile (Wasserbezug vom Zweckverband für die Wasserversorgung des Hügellandes zwischen Alb und Pfinz)
Parameter Value Parametric value Share of the parametric value Reference
Sum of 4 PFAS n.b. mg/l
not determined
Mean
Sum of PFAS n.b. mg/l
not determined
Mean

Indicator parameters (20)

Indicator parameters – Karlsruher Höhenstadtteile (Wasserbezug vom Zweckverband für die Wasserversorgung des Hügellandes zwischen Alb und Pfinz)
Parameter Value Parametric value Share of the parametric value Reference
Aluminium < 0,02 mg/l
below limit of quantification
0.2 mg/l
< 10 % *
Mean
Ammonium < 0,01 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Mean
Calcite dissolution capacity mg/l CaCO3
not determined
5 mg/l CaCO3 Mean
Chloride 16,6 mg/l 250 mg/l
7 %
Mean
Clostridium perfringens (including spores) 0 Anzahl/100 ml 0/100 ml Mean
Coliform bacteria 0 Anzahl/100 ml 0/100 ml Mean
Colony count 22 °C < 1 Anzahl/ml
below limit of quantification
ohne anormale Veränderung Mean
Colony count 36 °C < 1 Anzahl/ml
below limit of quantification
ohne anormale Veränderung Mean
Colour < 0,1 m-1
below limit of quantification
0.5 m⁻¹ Mean
Conductivity (25 °C) 654 μS/cm 2,790 µS/cm Mean
Iron < 0,01 mg/l
below limit of quantification
0.2 mg/l
< 5 % *
Mean
Manganese < 0,005 mg/l
below limit of quantification
50 µg/l
< 10 % *
Mean
Odour ohne für den Verbraucher annehmbar Mean
Oxidisability n.a. mg/l O2
not detectable
5 mg/l O2 Mean
pH 7,33 pH-Einheiten 6,5–9,5 Mean
Sodium 7,4 mg/l 200 mg/l
4 %
Mean
Sulphate 29,9 mg/l 250 mg/l
12 %
Mean
Taste ohne für den Verbraucher annehmbar Mean
Total organic carbon (TOC) 0,47 mg/l ohne anormale Veränderung Mean
Turbidity 0,10 Nephelometrische Trübungseinheiten (NTU) 1 NTU Mean

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Radiology (3)

Radiology – Karlsruher Höhenstadtteile (Wasserbezug vom Zweckverband für die Wasserversorgung des Hügellandes zwischen Alb und Pfinz)
Parameter Value Parametric value Share of the parametric value Reference
Indicative dose n.a. mSv/a
not detectable
0.1 mSv/a Mean
Radon-222 n.a. Bq/l
not detectable
100 Bq/l Mean
Tritium n.a. Bq/l
not detectable
100 Bq/l Mean

Further parameters (14)

Further parameters – Karlsruher Höhenstadtteile (Wasserbezug vom Zweckverband für die Wasserversorgung des Hügellandes zwischen Alb und Pfinz)
Parameter Value Parametric value Share of the parametric value Reference
Acid capacity to pH 4.3 5,79 mmol/l Mean
Base capacity to pH 8.2 0,60 mmol/l Mean
Calcite precipitation capacity 23 mg/l CaCO3 Mean
Calcium 2,46 mmol/l Mean
Carbonate hardness 2,78 mmol/l Mean
Hardness range (WRMG) hart Mean
Hydrogen carbonate 350 mg/l Mean
Magnesium 0,86 mmol/l Mean
Oxygen 9,1 mg/l Mean
Phosphate 0,04 mg/l Mean
Potassium 0,04 mmol/l Mean
Silicate / silicic acid 4,4 mg/l Mean
Spectral absorption coefficient 254 nm (SAC 254) 0,8 m-1 Mean
Total hardness 3,32 mmol/l Mean

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: www.stadtwerke-karlsruhe.de · Jahresmittelwerte 2025 · retrieved on 11/07/2026
Show 1 more supply zone in this postcode

Stadtwerke Karlsruhe gesamt

Stadtwerke Karlsruhe

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

Water hardness
18.3 °dH
Hardness range hart
Key values Stadtwerke Karlsruhe gesamt
Parameter Value Parametric value Share of the parametric value Reference
Sum of PFAS n.b. mg/l
not determined
Mean
Nitrate 3,6 mg/l 50 mg/l
7 %
Mean
Lead < 0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Escherichia coli (E. coli) 0 Anz./100 ml 0/100 ml Mean
Sulphate 44,8 mg/l 250 mg/l
18 %
Mean
Sodium 12,7 mg/l 200 mg/l
6 %
Mean

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Show all recorded parameters (73 — most recent value per parameter)

Microbiology (2)

Microbiology – Stadtwerke Karlsruhe gesamt
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) 0 Anz./100 ml 0/100 ml Mean
Intestinal enterococci 0 Anz./100 ml 0/100 ml Mean

Chemical parameters (32)

Chemical parameters – Stadtwerke Karlsruhe gesamt
Parameter Value Parametric value Share of the parametric value Reference
1,2-dichloroethane < 0,0001 mg/l
below limit of quantification
3 µg/l
< 3 % *
Mean
Acrylamide n.a. mg/l
not detectable
0.1 µg/l Mean
Antimony < 0,001 mg/l
below limit of quantification
5 µg/l
< 20 % *
Mean
Arsenic < 0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Benzene < 0,0001 mg/l
below limit of quantification
1 µg/l
< 10 % *
Mean
Benzo(a)pyrene < 0,000002 mg/l
below limit of quantification
10 ng/l
< 20 % *
Mean
Bisphenol A < 0,000005 mg/l
below limit of quantification
2.5 µg/l
< 0.2 % *
Mean
Boron < 0,02 mg/l
below limit of quantification
1 mg/l
< 2 % *
Mean
Bromate < 0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Cadmium < 0,0001 mg/l
below limit of quantification
3 µg/l
< 3 % *
Mean
Chlorate n.a. mg/l
not detectable
70 µg/l Mean
Chlorite n.a. mg/l
not detectable
0.2 mg/l Mean
Chromium < 0,0005 mg/l
below limit of quantification
25 µg/l
< 2 % *
Mean
Copper < 0,01 mg/l
below limit of quantification
2 mg/l
< 0.5 % *
Mean
Cyanide < 0,01 mg/l
below limit of quantification
50 µg/l
< 20 % *
Mean
Epichlorohydrin n.a. mg/l
not detectable
0.1 µg/l Mean
Fluoride < 0,05 mg/l
below limit of quantification
1.5 mg/l
< 3 % *
Mean
Haloacetic acids (HAA) n.a. mg/l
not detectable
Mean
Lead < 0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Mercury < 0,00005 mg/l
below limit of quantification
1 µg/l
< 5 % *
Mean
Microcystin-LR n.a. mg/l
not detectable
Mean
Nickel < 0,001 mg/l
below limit of quantification
20 µg/l
< 5 % *
Mean
Nitrate 3,6 mg/l 50 mg/l
7 %
Mean
Nitrite < 0,01 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Mean
Pesticides n.b. mg/l
not determined
0.1 µg/l Mean
Pesticides — Total n.b. mg/l
not determined
0.5 µg/l Mean
Polycyclic aromatic hydrocarbons n.b. mg/l
not determined
0.1 µg/l Mean
Selenium < 0,001 mg/l
below limit of quantification
10 µg/l
< 10 % *
Mean
Tetrachloroethene and Trichloroethene (sum) n.b. mg/l
not determined
10 µg/l Mean
Trihalomethanes — Total n.a. mg/l
not detectable
50 µg/l Mean
Uranium 0,0013 mg/l 10 µg/l
13 %
Mean
Vinyl chloride n.a. mg/l
not detectable
0.5 µg/l Mean

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

PFAS (2)

PFAS – Stadtwerke Karlsruhe gesamt
Parameter Value Parametric value Share of the parametric value Reference
Sum of 4 PFAS n.b. mg/l
not determined
Mean
Sum of PFAS n.b. mg/l
not determined
Mean

Indicator parameters (20)

Indicator parameters – Stadtwerke Karlsruhe gesamt
Parameter Value Parametric value Share of the parametric value Reference
Aluminium < 0,02 mg/l
below limit of quantification
0.2 mg/l
< 10 % *
Mean
Ammonium < 0,01 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Mean
Calcite dissolution capacity mg/l CaCO3
not determined
5 mg/l CaCO3 Mean
Chloride 25,2 mg/l 250 mg/l
10 %
Mean
Clostridium perfringens (including spores) n.a. Anzahl/100 ml
not detectable
0/100 ml Mean
Coliform bacteria 0 Anzahl/100 ml 0/100 ml Mean
Colony count 22 °C < 1 Anzahl/ml
below limit of quantification
ohne anormale Veränderung Mean
Colony count 36 °C < 1 Anzahl/ml
below limit of quantification
ohne anormale Veränderung Mean
Colour < 0,1 m-1
below limit of quantification
0.5 m⁻¹ Mean
Conductivity (25 °C) 660 μS/cm 2,790 µS/cm Mean
Iron < 0,01 mg/l
below limit of quantification
0.2 mg/l
< 5 % *
Mean
Manganese < 0,005 mg/l
below limit of quantification
50 µg/l
< 10 % *
Mean
Odour ohne für den Verbraucher annehmbar Mean
Oxidisability n.a. mg/l O2
not detectable
5 mg/l O2 Mean
pH 7,22 pH-Einheiten 6,5–9,5 Mean
Sodium 12,7 mg/l 200 mg/l
6 %
Mean
Sulphate 44,8 mg/l 250 mg/l
18 %
Mean
Taste ohne für den Verbraucher annehmbar Mean
Total organic carbon (TOC) 1,03 mg/l ohne anormale Veränderung Mean
Turbidity 0,11 Nephelometrische Trübungseinheiten (NTU) 1 NTU Mean

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Radiology (3)

Radiology – Stadtwerke Karlsruhe gesamt
Parameter Value Parametric value Share of the parametric value Reference
Indicative dose n.a. mSv/a
not detectable
0.1 mSv/a Mean
Radon-222 n.a. Bq/l
not detectable
100 Bq/l Mean
Tritium n.a. Bq/l
not detectable
100 Bq/l Mean

Further parameters (14)

Further parameters – Stadtwerke Karlsruhe gesamt
Parameter Value Parametric value Share of the parametric value Reference
Acid capacity to pH 4.3 5,48 mmol/l Mean
Base capacity to pH 8.2 0,74 mmol/l Mean
Calcite precipitation capacity 18 mg/l CaCO3 Mean
Calcium 2,85 mmol/l Mean
Carbonate hardness 2,71 mmol/l Mean
Hardness range (WRMG) hart Mean
Hydrogen carbonate 331 mg/l Mean
Magnesium 0,42 mmol/l Mean
Oxygen 6,4 mg/l Mean
Phosphate < 0,01 mg/l
below limit of quantification
Mean
Potassium 0,05 mmol/l Mean
Silicate / silicic acid 5,8 mg/l Mean
Spectral absorption coefficient 254 nm (SAC 254) 1,5 m-1 Mean
Total hardness 3,26 mmol/l Mean

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Frequent questions about postcode 76199

How hard is the water in Postcode 76199?
Stadtwerke Karlsruhe publishes a total hardness of 3,32 mmol/l for the supply zone Karlsruher Höhenstadtteile (Wasserbezug vom Zweckverband für die Wasserversorgung des Hügellandes zwischen Alb und Pfinz) — that corresponds to 18.6 °dH. The hardness range is a classification under the German Detergents and Cleaning Products Act (soft below 8,4 °dH, medium 8,4 to 14 °dH, hard above that) and not a quality verdict — it indicates how much calcium and magnesium is dissolved in the water. Basis: Publication by the water supplier, retrieved on 11/07/2026.
How much nitrate is in the drinking water in Postcode 76199?
Stadtwerke Karlsruhe publishes a nitrate value of 10,3 mg/l for the supply zone Karlsruher Höhenstadtteile (Wasserbezug vom Zweckverband für die Wasserversorgung des Hügellandes zwischen Alb und Pfinz). The statutory parametric value is 50 mg/l; the measured value represents 21 % of the parametric value. Basis: Publication by the water supplier, retrieved on 11/07/2026.
Who supplies the drinking water in Postcode 76199?
Stadtwerke Karlsruhe. The values shown here come from the supply zone Karlsruher Höhenstadtteile (Wasserbezug vom Zweckverband für die Wasserversorgung des Hügellandes zwischen Alb und Pfinz) and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.

General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.