Skip to content
maunawai.info

Drinking water in 67816

One supply zone, water supplier: TWIST RLP - AB Kerzenheim, VGW Göllheim (WW), TW.

How to read the share of the parametric value

12 % Share of the parametric value. The proportion of the permitted maximum that the measured value uses — here 12 %, so just over an eighth.
< 10 % * Below the limit of quantification. The substance was not detectable. The mark shows where the detection limit lies relative to the parametric value — the actual share of the parametric value is below that.

Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.

AB Kerzenheim, VGW Göllheim (WW), TW

TWIST RLP - AB Kerzenheim, VGW Göllheim (WW), TW

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

No date is given for these values. The water supplier publishes the analysis without a sampling date and without a report date. When the water was examined is not apparent from the source — we do not add a date and we do not estimate one. What is stated is therefore only when we retrieved the document.

Water hardness
11.1 °dH
Hardness range medium
Key values AB Kerzenheim, VGW Göllheim (WW), TW
Parameter Value Parametric value Share of the parametric value Reference
Sum of PFAS < 0.001 µg/L
below limit of quantification
0.1 µg/l
< 1 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Nitrate 21 mg/L 50 mg/l
42 %
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Lead < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Escherichia coli (E. coli) 0 Anzahl/100ml 0/100 ml Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Sulphate 17 mg/L 250 mg/l
7 %
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Sodium 7.5 mg/L 200 mg/l
4 %
Mean · AB Kerzenheim, VGW Göllheim (WW), TW

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Show all recorded parameters (30 — most recent value per parameter)

Microbiology (1)

Microbiology – AB Kerzenheim, VGW Göllheim (WW), TW
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) 0 Anzahl/100ml 0/100 ml Mean · AB Kerzenheim, VGW Göllheim (WW), TW

Chemical parameters (14)

Chemical parameters – AB Kerzenheim, VGW Göllheim (WW), TW
Parameter Value Parametric value Share of the parametric value Reference
Antimony < 1 µg/L
below limit of quantification
5 µg/l
< 20 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Arsenic < 0.5 µg/L
below limit of quantification
10 µg/l
< 5 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Boron 0.03 mg/L 1 mg/l
3 %
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Cadmium < 0.1 µg/L
below limit of quantification
3 µg/l
< 3 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Copper 0.005 mg/L 2 mg/l
0.3 %
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Cyanide < 0.005 mg/L
below limit of quantification
50 µg/l
< 10 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Fluoride < 0.1 mg/L
below limit of quantification
1.5 mg/l
< 7 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Lead < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Mercury < 0.1 µg/L
below limit of quantification
1 µg/l
< 10 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Nickel 1 µg/L 20 µg/l
5 %
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Nitrate 21 mg/L 50 mg/l
42 %
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Nitrite < 0.005 mg/L
below limit of quantification
0.5 mg/l
< 1 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Selenium < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Uranium 1.5 µg/L 10 µg/l
15 %
Mean · AB Kerzenheim, VGW Göllheim (WW), TW

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

PFAS (1)

PFAS – AB Kerzenheim, VGW Göllheim (WW), TW
Parameter Value Parametric value Share of the parametric value Reference
Sum of PFAS < 0.001 µg/L
below limit of quantification
0.1 µg/l
< 1 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Indicator parameters (10)

Indicator parameters – AB Kerzenheim, VGW Göllheim (WW), TW
Parameter Value Parametric value Share of the parametric value Reference
Aluminium < 0.005 mg/L
below limit of quantification
0.2 mg/l
< 3 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Ammonium < 0.05 mg/L
below limit of quantification
0.5 mg/l
< 10 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Chloride 18 mg/L 250 mg/l
7 %
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Coliform bacteria 0 Anzahl/100ml 0/100 ml Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Iron < 0.005 mg/L
below limit of quantification
0.2 mg/l
< 3 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Manganese < 0.005 mg/L
below limit of quantification
50 µg/l
< 10 % *
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
pH 7.59 - 6,5–9,5 Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Sodium 7.5 mg/L 200 mg/l
4 %
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Sulphate 17 mg/L 250 mg/l
7 %
Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Temperature 12.6 °C Mean · AB Kerzenheim, VGW Göllheim (WW), TW

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (4)

Further parameters – AB Kerzenheim, VGW Göllheim (WW), TW
Parameter Value Parametric value Share of the parametric value Reference
Calcium 51 mg/L Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Magnesium 14 mg/L Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Potassium 3.7 mg/L Mean · AB Kerzenheim, VGW Göllheim (WW), TW
Total hardness 1.98 mmol/l Mean · AB Kerzenheim, VGW Göllheim (WW), TW

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://geodaten-wasser.rlp-umwelt.de/twist/2392695024/trinkwasserqualitaet · Mittelwerte · retrieved on 13/07/2026

Frequent questions about postcode 67816

How hard is the water in Postcode 67816?
TWIST RLP - AB Kerzenheim, VGW Göllheim (WW), TW publishes a total hardness of 1.98 mmol/l for the supply zone AB Kerzenheim, VGW Göllheim (WW), TW — that corresponds to 11.1 °dH. The hardness range is a classification under the German Detergents and Cleaning Products Act (soft below 8,4 °dH, medium 8,4 to 14 °dH, hard above that) and not a quality verdict — it indicates how much calcium and magnesium is dissolved in the water. Basis: Publication by the water supplier, retrieved on 13/07/2026.
How much nitrate is in the drinking water in Postcode 67816?
TWIST RLP - AB Kerzenheim, VGW Göllheim (WW), TW publishes a nitrate value of 21 mg/L for the supply zone AB Kerzenheim, VGW Göllheim (WW), TW. The statutory parametric value is 50 mg/l; the measured value represents 42 % of the parametric value. Basis: Publication by the water supplier, retrieved on 13/07/2026.
Are PFAS detectable in the drinking water in Postcode 67816?
TWIST RLP - AB Kerzenheim, VGW Göllheim (WW), TW publishes for the supply zone AB Kerzenheim, VGW Göllheim (WW), TW a sum value PFAS-20 below the limit of quantification (entry in the report: "< 0.001 µg/L"). This is not to be read as "PFAS-free": below the limit of quantification, the measurement cannot make any statement. The statutory parametric value is 0.1 µg/l; the measured value lies below it and cannot be specified more precisely below the limit of quantification. For the sum of the 20 individual substances, this parametric value has applied since 12/01/2026. Basis: Publication by the water supplier, retrieved on 13/07/2026.
Who supplies the drinking water in Postcode 67816?
TWIST RLP - AB Kerzenheim, VGW Göllheim (WW), TW. The values shown here come from the supply zone AB Kerzenheim, VGW Göllheim (WW), TW and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.

General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.