Skip to content
maunawai.info

Drinking water in 53545

One supply zone, water supplier: TWIST RLP - Versorgungsgebiet AB Neuwied-Block.

How to read the share of the parametric value

12 % Share of the parametric value. The proportion of the permitted maximum that the measured value uses — here 12 %, so just over an eighth.
< 10 % * Below the limit of quantification. The substance was not detectable. The mark shows where the detection limit lies relative to the parametric value — the actual share of the parametric value is below that.

Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.

Versorgungsgebiet AB Neuwied-Block

TWIST RLP - Versorgungsgebiet AB Neuwied-Block

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

No date is given for these values. The water supplier publishes the analysis without a sampling date and without a report date. When the water was examined is not apparent from the source — we do not add a date and we do not estimate one. What is stated is therefore only when we retrieved the document.

Water hardness
15.2 °dH
Hardness range hard
Key values Versorgungsgebiet AB Neuwied-Block
Parameter Value Parametric value Share of the parametric value Reference
Sum of PFAS 0.024 µg/L 0.1 µg/l
24 %
Mean · Versorgungsgebiet AB Neuwied-Block
Nitrate 26 mg/L 50 mg/l
52 %
Mean · Versorgungsgebiet AB Neuwied-Block
Lead 1.7 µg/L 10 µg/l
17 %
Mean · Versorgungsgebiet AB Neuwied-Block
Escherichia coli (E. coli) 0 Anzahl/100ml 0/100 ml Mean · Versorgungsgebiet AB Neuwied-Block
Sulphate 44 mg/L 250 mg/l
18 %
Mean · Versorgungsgebiet AB Neuwied-Block
Sodium 46 mg/L 200 mg/l
23 %
Mean · Versorgungsgebiet AB Neuwied-Block
Show all recorded parameters (30 — most recent value per parameter)

Microbiology (1)

Microbiology – Versorgungsgebiet AB Neuwied-Block
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) 0 Anzahl/100ml 0/100 ml Mean · Versorgungsgebiet AB Neuwied-Block

Chemical parameters (14)

Chemical parameters – Versorgungsgebiet AB Neuwied-Block
Parameter Value Parametric value Share of the parametric value Reference
Antimony < 0.5 µg/L
below limit of quantification
5 µg/l
< 10 % *
Mean · Versorgungsgebiet AB Neuwied-Block
Arsenic < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Mean · Versorgungsgebiet AB Neuwied-Block
Boron < 0.1 mg/L
below limit of quantification
1 mg/l
< 10 % *
Mean · Versorgungsgebiet AB Neuwied-Block
Cadmium < 0.3 µg/L
below limit of quantification
3 µg/l
< 10 % *
Mean · Versorgungsgebiet AB Neuwied-Block
Copper < 0.05 mg/L
below limit of quantification
2 mg/l
< 3 % *
Mean · Versorgungsgebiet AB Neuwied-Block
Cyanide 0.011 mg/L 50 µg/l
22 %
Mean · Versorgungsgebiet AB Neuwied-Block
Fluoride 0.27 mg/L 1.5 mg/l
18 %
Mean · Versorgungsgebiet AB Neuwied-Block
Lead 1.7 µg/L 10 µg/l
17 %
Mean · Versorgungsgebiet AB Neuwied-Block
Mercury < 0.1 µg/L
below limit of quantification
1 µg/l
< 10 % *
Mean · Versorgungsgebiet AB Neuwied-Block
Nickel < 2 µg/L
below limit of quantification
20 µg/l
< 10 % *
Mean · Versorgungsgebiet AB Neuwied-Block
Nitrate 26 mg/L 50 mg/l
52 %
Mean · Versorgungsgebiet AB Neuwied-Block
Nitrite < 0.05 mg/L
below limit of quantification
0.5 mg/l
< 10 % *
Mean · Versorgungsgebiet AB Neuwied-Block
Selenium < 1 µg/L
below limit of quantification
10 µg/l
< 10 % *
Mean · Versorgungsgebiet AB Neuwied-Block
Uranium 2 µg/L 10 µg/l
20 %
Mean · Versorgungsgebiet AB Neuwied-Block

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

PFAS (1)

PFAS – Versorgungsgebiet AB Neuwied-Block
Parameter Value Parametric value Share of the parametric value Reference
Sum of PFAS 0.024 µg/L 0.1 µg/l
24 %
Mean · Versorgungsgebiet AB Neuwied-Block

Indicator parameters (10)

Indicator parameters – Versorgungsgebiet AB Neuwied-Block
Parameter Value Parametric value Share of the parametric value Reference
Aluminium < 0.02 mg/L
below limit of quantification
0.2 mg/l
< 10 % *
Mean · Versorgungsgebiet AB Neuwied-Block
Ammonium < 0.05 mg/L
below limit of quantification
0.5 mg/l
< 10 % *
Mean · Versorgungsgebiet AB Neuwied-Block
Chloride 54 mg/L 250 mg/l
22 %
Mean · Versorgungsgebiet AB Neuwied-Block
Coliform bacteria 0 Anzahl/100ml 0/100 ml Mean · Versorgungsgebiet AB Neuwied-Block
Iron < 0.02 mg/L
below limit of quantification
0.2 mg/l
< 10 % *
Mean · Versorgungsgebiet AB Neuwied-Block
Manganese < 0.005 mg/L
below limit of quantification
50 µg/l
< 10 % *
Mean · Versorgungsgebiet AB Neuwied-Block
pH 7.52 - 6,5–9,5 Mean · Versorgungsgebiet AB Neuwied-Block
Sodium 46 mg/L 200 mg/l
23 %
Mean · Versorgungsgebiet AB Neuwied-Block
Sulphate 44 mg/L 250 mg/l
18 %
Mean · Versorgungsgebiet AB Neuwied-Block
Temperature 15 °C Mean · Versorgungsgebiet AB Neuwied-Block

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Further parameters (4)

Further parameters – Versorgungsgebiet AB Neuwied-Block
Parameter Value Parametric value Share of the parametric value Reference
Calcium 72 mg/L Mean · Versorgungsgebiet AB Neuwied-Block
Magnesium 17 mg/L Mean · Versorgungsgebiet AB Neuwied-Block
Potassium 11 mg/L Mean · Versorgungsgebiet AB Neuwied-Block
Total hardness 2.71 mmol/l Mean · Versorgungsgebiet AB Neuwied-Block

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Source: https://geodaten-wasser.rlp-umwelt.de/twist/2716695060/trinkwasserqualitaet · Mittelwerte · retrieved on 13/07/2026

Frequent questions about postcode 53545

How hard is the water in Postcode 53545?
TWIST RLP - Versorgungsgebiet AB Neuwied-Block publishes a total hardness of 2.71 mmol/l for the supply zone Versorgungsgebiet AB Neuwied-Block — that corresponds to 15.2 °dH. The hardness range is a classification under the German Detergents and Cleaning Products Act (soft below 8,4 °dH, medium 8,4 to 14 °dH, hard above that) and not a quality verdict — it indicates how much calcium and magnesium is dissolved in the water. Basis: Publication by the water supplier, retrieved on 13/07/2026.
How much nitrate is in the drinking water in Postcode 53545?
TWIST RLP - Versorgungsgebiet AB Neuwied-Block publishes a nitrate value of 26 mg/L for the supply zone Versorgungsgebiet AB Neuwied-Block. The statutory parametric value is 50 mg/l; the measured value represents 52 % of the parametric value. Basis: Publication by the water supplier, retrieved on 13/07/2026.
Are PFAS detectable in the drinking water in Postcode 53545?
TWIST RLP - Versorgungsgebiet AB Neuwied-Block publishes for the supply zone Versorgungsgebiet AB Neuwied-Block a sum value PFAS-20 of 0.024 µg/L. The statutory parametric value is 0.1 µg/l; the measured value represents 24 % of the parametric value. For the sum of the 20 individual substances, this parametric value has applied since 12/01/2026. Basis: Publication by the water supplier, retrieved on 13/07/2026.
Who supplies the drinking water in Postcode 53545?
TWIST RLP - Versorgungsgebiet AB Neuwied-Block. The values shown here come from the supply zone Versorgungsgebiet AB Neuwied-Block and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.

General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.