Drinking water in 02894

One supply zone, water supplier: Trinkwasserversorgung (Wasserwerke Diehsa, Trebus, Leipgen, Niesky, Rietschen, Uhsmannsdorf).

How to read the share of the parametric value

12 % Share of the parametric value. The proportion of the permitted maximum that the measured value uses — here 12 %, so just over an eighth.
< 10 % * Below the limit of quantification. The substance was not detectable. The mark shows where the detection limit lies relative to the parametric value — the actual share of the parametric value is below that.

Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.

Assigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.

No date is given for these values. The water supplier publishes the analysis without a sampling date and without a report date. When the water was examined is not apparent from the source — we do not add a date and we do not estimate one. What is stated is therefore only when we retrieved the document.

Water hardness
9.5 °dH
Hardness range medium
Key values Diehsa / Trebus / Leipgen / Niesky / Rietschen / Uhsmannsdorf
Parameter Value Parametric value Share of the parametric value Reference
Nitrate 2,3 mg/l 50 mg/l
5 %
Single value · WW Uhsmannsdorf (23.07.2025)
Lead <0,000721 mg/l
below limit of quantification
10 µg/l
< 7 % *
Single value · WW Uhsmannsdorf (23.07.2025)
Escherichia coli (E. coli) 0 Anzahl / 100 ml 0/100 ml Single value · WW Uhsmannsdorf (23.07.2025)
Sulphate 44 mg/l 250 mg/l
18 %
Single value · WW Uhsmannsdorf (23.07.2025)
Sodium 9,9 mg/l 200 mg/l
5 %
Single value · WW Uhsmannsdorf (23.07.2025)

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Show all recorded parameters (27 — most recent value per parameter)

Microbiology (2)

Microbiology – Diehsa / Trebus / Leipgen / Niesky / Rietschen / Uhsmannsdorf
Parameter Value Parametric value Share of the parametric value Reference
Escherichia coli (E. coli) 0 Anzahl / 100 ml 0/100 ml Single value · WW Uhsmannsdorf (23.07.2025)
Intestinal enterococci 0 Anzahl / 100 ml 0/100 ml Single value · WW Uhsmannsdorf (23.07.2025)

Chemical parameters (14)

Chemical parameters – Diehsa / Trebus / Leipgen / Niesky / Rietschen / Uhsmannsdorf
Parameter Value Parametric value Share of the parametric value Reference
Antimony <0,00004 mg/l
below limit of quantification
5 µg/l
< 0.8 % *
Single value · WW Uhsmannsdorf (23.07.2025)
Arsenic <0,0005 mg/l
below limit of quantification
10 µg/l
< 5 % *
Single value · WW Uhsmannsdorf (23.07.2025)
Boron 0,006 mg/l 1 mg/l
0.6 %
Single value · WW Uhsmannsdorf (23.07.2025)
Cadmium <0,000125 mg/l
below limit of quantification
3 µg/l
< 4 % *
Single value · WW Uhsmannsdorf (23.07.2025)
Chromium <0,002 mg/l
below limit of quantification
25 µg/l
< 8 % *
Single value · WW Uhsmannsdorf (23.07.2025)
Copper <0,007 mg/l
below limit of quantification
2 mg/l
< 0.4 % *
Single value · WW Uhsmannsdorf (23.07.2025)
Cyanide <0,005 mg/l
below limit of quantification
50 µg/l
< 10 % *
Single value · WW Uhsmannsdorf (23.07.2025)
Lead <0,000721 mg/l
below limit of quantification
10 µg/l
< 7 % *
Single value · WW Uhsmannsdorf (23.07.2025)
Mercury <0,0001 mg/l
below limit of quantification
1 µg/l
< 10 % *
Single value · WW Uhsmannsdorf (23.07.2025)
Nickel 0,006 mg/l 20 µg/l
30 %
Single value · WW Uhsmannsdorf (23.07.2025)
Nitrate 2,3 mg/l 50 mg/l
5 %
Single value · WW Uhsmannsdorf (23.07.2025)
Nitrite <0,01 mg/l
below limit of quantification
0.5 mg/l
< 2 % *
Single value · WW Uhsmannsdorf (23.07.2025)
Selenium <0,000332 mg/l
below limit of quantification
10 µg/l
< 3 % *
Single value · WW Uhsmannsdorf (23.07.2025)
Uranium <0,000066 mg/l
below limit of quantification
10 µg/l
< 0.7 % *
Single value · WW Uhsmannsdorf (23.07.2025)

* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.

Indicator parameters (7)

Indicator parameters – Diehsa / Trebus / Leipgen / Niesky / Rietschen / Uhsmannsdorf
Parameter Value Parametric value Share of the parametric value Reference
Aluminium 0,005 mg/l 0.2 mg/l
3 %
Single value · WW Uhsmannsdorf (23.07.2025)
Chloride 21 mg/l 250 mg/l
8 %
Single value · WW Uhsmannsdorf (23.07.2025)
Coliform bacteria 0 Anzahl / 100 ml 0/100 ml Single value · WW Uhsmannsdorf (23.07.2025)
Manganese 0,005 mg/l 50 µg/l
10 %
Single value · WW Uhsmannsdorf (23.07.2025)
Sodium 9,9 mg/l 200 mg/l
5 %
Single value · WW Uhsmannsdorf (23.07.2025)
Sulphate 44 mg/l 250 mg/l
18 %
Single value · WW Uhsmannsdorf (23.07.2025)
Taste ohne mg/l für den Verbraucher annehmbar Single value · WW Uhsmannsdorf (23.07.2025)

Further parameters (4)

Further parameters – Diehsa / Trebus / Leipgen / Niesky / Rietschen / Uhsmannsdorf
Parameter Value Parametric value Share of the parametric value Reference
Calcium 53,2 mg/l Single value · WW Uhsmannsdorf (23.07.2025)
Magnesium 3,38 mg/l Single value · WW Uhsmannsdorf (23.07.2025)
Potassium 2,54 mg/l Single value · WW Uhsmannsdorf (23.07.2025)
Total hardness 1,7 mmol/l Single value · WW Leipgen (11.05.2026)

Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.

Frequent questions about postcode 02894

How hard is the water in Postcode 02894?
Trinkwasserversorgung (Wasserwerke Diehsa, Trebus, Leipgen, Niesky, Rietschen, Uhsmannsdorf) publishes a total hardness of 1,7 mmol/l for the supply zone Diehsa / Trebus / Leipgen / Niesky / Rietschen / Uhsmannsdorf — that corresponds to 9.5 °dH. The hardness range is a classification under the German Detergents and Cleaning Products Act (soft below 8,4 °dH, medium 8,4 to 14 °dH, hard above that) and not a quality verdict — it indicates how much calcium and magnesium is dissolved in the water. Basis: Publication by the water supplier, retrieved on 13/07/2026.
How much nitrate is in the drinking water in Postcode 02894?
Trinkwasserversorgung (Wasserwerke Diehsa, Trebus, Leipgen, Niesky, Rietschen, Uhsmannsdorf) publishes a nitrate value of 2,3 mg/l for the supply zone Diehsa / Trebus / Leipgen / Niesky / Rietschen / Uhsmannsdorf. The statutory parametric value is 50 mg/l; the measured value represents 5 % of the parametric value. Basis: Publication by the water supplier, retrieved on 13/07/2026.
Who supplies the drinking water in Postcode 02894?
Trinkwasserversorgung (Wasserwerke Diehsa, Trebus, Leipgen, Niesky, Rietschen, Uhsmannsdorf). The values shown here come from the supply zone Diehsa / Trebus / Leipgen / Niesky / Rietschen / Uhsmannsdorf and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.

General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.