Drinking water in 2606 (Switzerland)
The drinking water in Postcode 2606 has a total hardness of 11.3 °dH. Nitrate reaches 3,9 mg/l, the statutory parametric value is 40 mg/l. Measured in supply zone Corgémont of Commune de Corgémont, retrieved on 12/08/2026.
One supply zone, water supplier: Commune de Corgémont.
The values come from the SVGW platform trinkwasser.ch. Water utilities report there voluntarily; the SVGW does not verify the data. For each parameter, the minimum, maximum, average and median of one year are published; hardness in French degrees (°fH). On 20 August 2026 the SVGW objected in writing to the use of this data for maunawai.info: we do not show values from this source, but only name the parameters measured there. Analyses we obtained directly from the water supplier are shown in full.
How to read the share of the parametric value
Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.
Corgémont
Commune de CorgémontAssigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.
No date is given for these values. The water supplier publishes the analysis without a sampling date and without a report date. When the water was examined is not apparent from the source — we do not add a date and we do not estimate one. What is stated is therefore only when we retrieved the document.
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Nitrate | 3,9 mg/l | 40 mg/l | 10 % | Single value |
| Sulphate | 3,4 mg/l | — | — | Single value |
Show all recorded parameters (9 — most recent value per parameter)
Chemical parameters (2)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Nitrate | 3,9 mg/l | 40 mg/l | 10 % | Single value |
| Nitrite | non décelable not detectable Unit not stated in the document | 0.1 mg/l | — | Single value |
Indicator parameters (4)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Ammonium | non décelable not detectable Unit not stated in the document | 0.5 mg/l | — | Single value |
| Chloride | 0,9 mg/l | — | — | Single value |
| Sulphate | 3,4 mg/l | — | — | Single value |
| Turbidity | 0,3 NTU | — | — | Single value |
Further parameters (3)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Calcium | 76,2 mg/l | — | — | Single value |
| Magnesium | 2,9 mg/l | — | — | Single value |
| Total hardness | 2,02 mmol/l | — | — | Single value |
Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.
Frequent questions about postcode 2606
- How hard is the water in Postcode 2606?
- Commune de Corgémont publishes a total hardness of 2,02 mmol/l for the supply zone Corgémont — that corresponds to 11.3 °dH. Hardness indicates how much calcium and magnesium are dissolved in the water. It is not a quality assessment: there is no parametric value for hardness. Basis: Publication by the water supplier, retrieved on 12/08/2026.
- How much nitrate is in the drinking water in Postcode 2606?
- Commune de Corgémont publishes a nitrate value of 3,9 mg/l for the supply zone Corgémont. The statutory parametric value is 40 mg/l; the measured value represents 10 % of the parametric value. Basis: Publication by the water supplier, retrieved on 12/08/2026.
- Who supplies the drinking water in Postcode 2606?
- Commune de Corgémont. The values shown here come from the supply zone Corgémont and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.
General questions — how current the data is, limit of quantification, parametric values, who is behind this site — are answered under Questions & answers.