Drinking water in 4202 (Austria)
One supply zone, water supplier: Wasserverband Fernwasserversorgung Mühlviertel.
The values come from the Austrian drinking water database, to which water suppliers report voluntarily. In each case the highest value of the published range is given.
How to read the share of the parametric value
Several samples per year: for chemical parameters the mean value is given, for microbiological ones the highest measured value. There the parametric value is zero — a single finding would disappear in the average, and it is precisely that finding which is the information. Which reference applies is stated in the last column of the table.
Alberndorf, Altenberg, Eidenberg, Gramastetten, Haibach, Hellmonsödt, Herzogsdorf, Kirchschlag bei Linz, Lichtenberg und Sonnberg im Mühlkreis
Wasserverband Fernwasserversorgung MühlviertelAssigned via the water supplier — the exact supply zone boundary within the postcode is not yet linked.
These values are more than a year old. The most recent analysis the water supplier has published for this zone dates from 04/06/2025. We have no newer values — which is why we show the latest available ones rather than none at all. They say nothing about how the water has changed since then.
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Nitrate | 9,40 mg/l | 50 mg/l | 19 % | Single value |
| Sulphate | 11,00 mg/l | 250 mg/l | 4 % | Single value |
| Sodium | 8,00 mg/l | 200 mg/l | 4 % | Single value |
Show all recorded parameters (21 — most recent value per parameter)
Microbiology (1)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Intestinal enterococci | 0 KBE/100 ml | 0/100 ml | — | Single value |
Chemical parameters (2)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Nitrate | 9,40 mg/l | 50 mg/l | 19 % | Single value |
| Nitrite | <0,02 mg/l below limit of quantification | 0.1 mg/l | < 20 % * | Single value |
* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.
Indicator parameters (12)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Ammonium | < 0,04 mg/l below limit of quantification | 0.5 mg/l | < 8 % * | Single value |
| Chloride | 12,00 mg/l | 200 mg/l | 6 % | Single value |
| Coliform bacteria | 0 KBE/100 ml | 0/100 ml | — | Single value |
| Colour | klar, farblos | — | — | Single value |
| Conductivity (25 °C) | 223 µS/cm | 2,500 µS/cm | — | Single value |
| Iron | < 0,03 mg/l below limit of quantification | 0.2 mg/l | < 15 % * | Single value |
| Manganese | < 0,01 mg/l below limit of quantification | 50 µg/l | < 20 % * | Single value |
| Odour | kein | — | — | Single value |
| pH | 7,74 | 6,5–9,5 | — | Single value |
| Sodium | 8,00 mg/l | 200 mg/l | 4 % | Single value |
| Sulphate | 11,00 mg/l | 250 mg/l | 4 % | Single value |
| Temperature | 12,00 ° C | — | — | Single value |
* Value below the limit of quantification: the actual share of the parametric value is not known; it lies somewhere below the stated upper bound. The marker shows where the limit of quantification of the measurement lies relative to the parametric value.
Further parameters (6)
| Parameter | Value | Parametric value | Share of the parametric value | Reference |
|---|---|---|---|---|
| Acid capacity to pH 4.3 | 2,10 mmol/l | — | — | Single value |
| Calcium | 36,90 mg/l | 400 mg/l | 9 % | Single value |
| Carbonate hardness | 5,80 ° dH | — | — | Single value |
| Magnesium | 6,60 mg/l | 150 mg/l | 4 % | Single value |
| Potassium | 2,30 mg/l | 50 mg/l | 5 % | Single value |
| Total hardness | 6,70 ° dH | — | — | Single value |
Values taken unchanged from the publications linked below — for each parameter the most recent recorded value. „—" in the parametric value column: no currently valid legal parametric value is stored in our database for this parameter; the parameter register with all parametric values is being expanded continuously.
Frequent questions about postcode 4202
- How hard is the water in Postcode 4202?
- Wasserverband Fernwasserversorgung Mühlviertel publishes a total hardness of 6.7 °dH for the supply zone Alberndorf, Altenberg, Eidenberg, Gramastetten, Haibach, Hellmonsödt, Herzogsdorf, Kirchschlag bei Linz, Lichtenberg und Sonnberg im Mühlkreis. Hardness indicates how much calcium and magnesium are dissolved in the water. It is not a quality assessment: there is no parametric value for hardness. Basis: Publication by the water supplier, retrieved on 11/08/2026.
- How much nitrate is in the drinking water in Postcode 4202?
- Wasserverband Fernwasserversorgung Mühlviertel publishes a nitrate value of 9,40 mg/l for the supply zone Alberndorf, Altenberg, Eidenberg, Gramastetten, Haibach, Hellmonsödt, Herzogsdorf, Kirchschlag bei Linz, Lichtenberg und Sonnberg im Mühlkreis. The statutory parametric value is 50 mg/l; the measured value represents 19 % of the parametric value. Basis: Publication by the water supplier, retrieved on 11/08/2026.
- Who supplies the drinking water in Postcode 4202?
- Wasserverband Fernwasserversorgung Mühlviertel. The values shown here come from the supply zone Alberndorf, Altenberg, Eidenberg, Gramastetten, Haibach, Hellmonsödt, Herzogsdorf, Kirchschlag bei Linz, Lichtenberg und Sonnberg im Mühlkreis and apply to the water the supplier delivers. What happens between the building connection and the tap — in old lead pipes, for example — is not covered by these analyses; information on that is provided by owners, the health authority or an examination by an accredited laboratory.